Connecting Gas Service - Dunkirk D247 Installation Instructions Manual

Gas-fired steam or vvater boiler
Table of Contents

Advertisement

CONNECTING GAS SERVICE
Connect gas service from meter to control assembly(s) in
accordance with ANSI Z223.1 1984 and local codes or utility
On multiple base boilers, connect gas service with branch
lines from common main. Individual branch lines must be
the same size as the inlet to the gas valve. A ground joint
union should be installed in each branch line for easy
servicing of gas controls. A drip leg or trap should be
installed at the bottom of a vertical section of piping at the
inlet to the control chain, Figure
8. A pipe compound
resistant to the action of liquefied petroleum gases must
be used on all threaded pipe connections.
The main gas supply line should be adequate to prevent
undue pressure drop. See Chart No. 3 for pipe sizes for
gas mains.
To check for leaks in gas piping, use a soap and water
solution or other approved
method, DO NOT USE AN
OPEN FLAME.
The boiler must be disconnected from the gas supply piping
system during any pressure testing of that system. Test
the gas connection to the boiler before placing the boiler in
operation.
Minimum Gas Supply Pressure
Models
300,500,600,
1000, 1300,
1500,2000,2100,2500,
2600,3000
Models
400, 700, 800,900, 1100,
1200,1400,1600,1700,
1800, 1900, 2200, 2300,
2400, 2700, 2800, 2900
Maximum Gas Supply Pressure
All Models
Manifold Pressure
All Models
GAS SUPPLY
l
5.0 inches w.c.
5.3 inches w.c.
14.0 inches w.c.
3.5 inches w.c.
SECURE MANIFOLD
FROM
BVER
HEAD
FRAMING
DRIP LEG
INSTALL
MANUAL
VALVES
5 FEET
ABOVE
FLOOR
WHERE
REQUIRED
BY
LOCAL
CODES
TYPICAL
ISOMETRIC
WIRING
AND
GAS
MAIN PIPING
NOT FURNISHED,
BOILERS
ARE FIELD
WIRED
AND
ASSEMBLED.
FIGURE 8
SUGGESTED
WIRING
AND GAS MAIN PIPING
CHART 3
TABLE OF PIPE SIZES IN INCHES FOR GAS MAINS
(NATURAL GAS)
Boiler
No.
20'
30'
40'
50'
60' 80' 100'
125' 150'
300
1¼ 1¼
400
1½ 1½
2
500
1½ 1½
2
2
2
600
2
2
2
2
2
700
2
2
2
2
2
800
2
2
2
2
2
900
2
2
2
2
2
1000
2
2
2
2
1100
2
2
2
2
2
1200
2
2
2
2
2½ 2½
3
1300
2
2
2
2½ 2½
3
3
1400
2
2
2
2½ 2½
3
3
3
1500
2
2
2½ 2½
3
3
3
1600
2
2
2½ 2½
3
3
3
1700
2
3
3
3
3
1800
2
3
3
3
3
1900
2
3
3
3
3
3
2000
2
3
3
3
3
3
2100
3
3
3
3
3
4
2200
3
3
3
3
4
4
2300
3
3
3
3
3
4
4
2400
3
3
3
3
3
4
4
2500
3
3
3
3
3
4
4
4
2600
3
3
3
3
3
4
4
4
4
2700
3
3
3
3
4
4
4
4
4
2800
3
3
3
4
4
4
4
4
4
2900
3
3
4
4
4
4
4
4
4
3000
3
4
4
4
4
4
4
4
4
SEE
CHART
# 3 FRR
GAS
MAIN MANIFRLD
SIZING
PROVIDE
DISCONNECT
MEANS
AND OVERLOAD
PROTECTION
AS REQUIRED
1202V
GOHz
4x4x5/8
JUNCTION
BOX
(BY INSTALLER)
MOUNT
IN
CONVENIENT
LOCATION
ADJACENT
TO BOILER
ALL
WIRING
TB CONFORM
TO
NEC
FOR
TEMPERATURE
LIMITATION
FOR
TYPE
"T*
WIRE
(63F
RISE)
ALL
WIRING
MUST
COMPLY
WITH
ALL
APPLICABLE
CODES,
REGULATIONS
10
AND
ORDINANCES