TURN GAS SUPPLY OFF.
TURN THERMOSTAT
(CONTROLLER)
TO CALL
FOR HEAT
POWER TO MODULE
(24V MODULE)
S8600 INTERMITTENT
PILOT SYSTEM
TROUBLESHOOTING
TABLE
START
I
NOTE: Before troubleshooting,
familiarize
yourself with the startup and check procedure.
Check line voltage power, low voltage transformer,
limit controller, thermostat
(controller) I
and wiring.
Also, check air proving switch on combustion air blower system (if used) and
that vent damper (if used) is open and end switch is made.
I
YES ,
SPARK ACROSS
IGNITER/SENSOR
GAP
YES
1
TURN GAS SUPPLY ON
PILOT BURNER LIGHTS?
YES
1
SPARK STOPS WHEN
PILOT IS LIT?
YES
r
MAIN BURNER LIGHTS?
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS
YES
r
I
CALL FOR HEAT ENDS
SYSTEM SHUTS OFF?
I
YES J ,
TROUBLESHOOTING
ENDS
Pull ignition lead and check
,,_ _
'_
•
On models with vent damper plug,
spark at module.
_f
make sure vent damper has not
been installed, then removed.
Spark okay?
Replace vent damper if necessary.
YES
Jr
On other models, replace module.
¥
I
•
Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
I
•
Check boot of the ignition cable for signs of melting or bucking.
Take protective
I
action to shield cable and boot from excessive temperatures.
•
Check that all manual
valves are
supply tubing and
are
gas
open,
pressures
good, and pilot burner orifice is not blocked.
•
Check electrical connection between module and pilot operator on gas control.
•
Check for 24 Vac across PV-MV/PV terminals on module.
If voltage is okay,
replace gas control: if not, replace module.
NOTE: If S8600B, H goes into lockout, reset system.
For S8600M, wait 6 min. nom.
for retry or reset system.
•
Check continuity of ignition cable and ground wire.
•
Clean flame rod.
•
Check electrical connections
between flame rod and module.
•
Check for cracked ceramic flame rod insulator.
•
Check that pilot flame covers flame rod and is steady and blue.
•
Adjust pilot flame.
•
If problem persists, replace module.
•
Check for 24 Mac across MV-MV/PV terminals.
If no voltage, replace module.
•
Check electrical connections
between module and gas control.
If okay, replace
gas control or gas control operator.
I
NOTE: If S8600B, H; $8610B, H goes into lockout, reset system.
For S8600M, wait
6 min. nom. For retry or reset system.
•
Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdowns may occur occasionally
even though operation is normal at the time of checkout.
•
Check that pilot flame covers flame rod and is steady and blue.
•
If checks okay, replace module.
•
Check for proper thermostat (controller) operation.
•
Remove MV lead at module: if valve closes, recheck temperature controller and
wiring: if not, replace gas control.
I
I
Repeat procedure
until trouble free operation is obtained.