UR = User Reset, AR = Automatic Reset, ARP = Automatic Reset after Power Down
NOTE: An automatic reset is only done if the fault condition has cleared.
Error code: Display
280 : Engine dome overtemp
282: G83/ENS/G1M
285: Alternator Short
287: Eng head under temp
298: False flame engine
299: False flame supplementary
300: Eng head under temp
301: Eng head over temp
302: Eng head thermocouple
303: Control thermocouple
304: Limit thermocouple
309: Power fail detection
310: Power monitor comm.
311: EGC comm. failure
421: Eng bu exc temp diff h'ex
422: BCU Eng bu inconsistent
423: BCU Supp bu inconsistent
424: Rep. loss of flame Eng bu
425: Rep. loss of flame Supp bu
This is a shortened list of the error codes, which will be displayed on the Programmer or on the room unit. If more than one error is active, the one with the
higher priority or the one that appeared first will be displayed.
Error codes 157,274,261,262 and 300 can be reset by the user by pressing the user reset button for 2 seconds, turning the dial to alter the flashing NO to a YES
and then pressing the OK button. After a few seconds the error should clear enabling a restart of the appliance. Errors 261 and 262 may indicate a problem with
the gas supply.
Errors 157,164,274 and 300 may indicate a problem with the central heating water fill or pump. If the problem persists contact the installer with the error code.
Error 158 indicates a possible blockage in the condense drain.
Error codes 10 through to 99 (except 97) are linked to installation and commissioning of your system and as such you should contact your installer to complete
commissioning.
Error codes that are shown as automatic reset will disappear once the fault has cleared. The appliance will restart if there is a demand except in the case of
errors 263 and 264 when the appliance must be switched off and on again to enable a restart.
All other error codes indicate a fault condition, which will require the attention of a service engineer.
© Baxi Heating UK Ltd 2010
Description
Engine dome overtemp has operated
G83/ENS module has detected an unhealthy mains condition
Power monitor IC has detected a short-circuit condition
Engine head temperature thermocouple measurement below
103 degrees C when the CX relay is energised
Ionisation probe of engine burner detected false flame
Ionisation probe of supplementary burner detected false flame
Engine head control temperature less than 150 degrees C when
CX relay is energised
Engine head control temperature greater than 540 degrees C
Magnitude of the difference between the engine head control
and limit thermocouples is greater than 100 degrees C
Engine head control thermocouple failure
Engine head limit thermocouple failure
Power failure to fan detected 24v dc supply
No data received from the power meter IC in the last 10 seconds
or the power monitor failed to register with the EGC
microcontroller within 10 seconds of power up
Communication timeout or communication failure
Engine burner excessive temperature difference across the
heat exchanger
Transmitted state of the engine burner BCU isn't consistent
Transmitted state of the supplementary burner BCU isn't consistent
Repeated loss of flame engine burner
repeated loss of flame supplementary burner
11.0 Error Codes
11.1
List of Error Codes (cont)
Lockout/reset action
Eng
AR
AR
AR
AR
AR
UR
AR
UR
UR
UR
AR
AR
AR
AR
AR
UR
Sup
AR
AR
UR
19