Electrical Connection

The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified installer and
must meet all local codes.
Make sure the household breaker is shut off prior to working on any electrical lines.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of
local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
The electrical line must be a min. 14 gauge, and supply 120 Volts, 60 Hz, and 5.7 Amps.
Route the electrical connection through the junction box cover plate and attach to the hookup wires pictured
below.
Caution:
Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Do not connect 110-120 VAC to the gas control valve or wiring system of this fireplace.
Electrical Junction Box Location
1
© Travis Industries
Installation
(for qualified installers only)
2
9/25/18 - 1488
a
11" (280mm)
2-1/4" (58mm)
b
a
3
b
4
PB36 CF Install