Electromelt power connection and end seal kit

Advertisement

21
note: see step 1 for proper heating techniques.
• Position the heat-shrinkable cap (Item B)
over the second mastic sheet. Push it all the
way down.
• Heat the cap until it shrinks completely.
iMportAnt: If cap starts to slide off end while shrinking,
pull it back in place and hold until it cools.
22
• Cut second mastic sheet (Item J) into two pieces. 3 in x 6
in (76 mm x 152 mm)
23
• Secure all wires 2 in (51 mm) from end
of outer jacket using cable tie (Item I).
• Position braid connection next to cap.
• Wrap braid connection and 1/2 in (13
mm) of outer jacket with 3 in x 6 in (76
mm x 152 mm) mastic sheet (Item J).
tHerMAl builDing solutions
3 in
(76 mm)
Braid
connection
Raychem-IM-H57284-EMKXP-EN-1612
6 in
(152 mm)
3 in
Trim
(76 mm)
Cable tie
½ in
(13 mm)
2 in
(51 mm)
Pinch and
squeeze mastic
6 / 10