Water sensing cable for suspended pipe

Advertisement

Quick Links

trAcetek
Water SenSing Cable for SuSpended pipe inStallation inStruCtionS
tools requireD
Wire cutters
Used to cut off tie wrap ends
TT-PTB-1000
Portable Test Box, battery powered instrument
(PN 486437-000)
designed for testing and troubleshooting TraceTek
systems
Digital multimeter
Can be used as an alternative or supplement to the
PTB. Meter must have 20 MΩ range
TT-MAPPING CAP-PC
Used to simulate leaks at connector points during
(PN P000000872)
commissioning and mapping process
Extra TT-MLC-PC
Leader cable. Used with the ohmmeter to make
(PN 683262-000)
easier connections to the sensor cable for resistance
measurements
Extra TT-MET-PC
End termination. Used during installation or trouble
(PN 169905-000)
shooting to temporarily isolate a sub-section of sen-
sor cable for resistance measurements
GENERAL NOTES: DO'S AND DON'TS:
Do:
• Store the cable in its original container in a clean, dry area until ready to install.
• Clean the pipe surface where the cable will be installed.
• Schedule the sensor cable installation as late as possible in the construction schedule to avoid risk
of damage or contamination by other contractors or construction tasks.
• Remove cable from the pipe if any thread cutting, welding, soldering or similar pipe fitting work will
be performed.
THERMAL BUILDING &
INDUSTRIAL HEAT TRACING SOLUTIONS
TT1100-OHP
EN-TraceTekTT1100OHP-IM-H58263      01/15
Description
These Instructions explain the proper procedures for installing and
testing TraceTek TT1100-OHP sensing cables. TT1100-OHP sensing
cables are primarily intended for use on overhead piping to detect a water
leak originating from a small pin hole or crack in the pipe. The wicking
action of the absorptive synthetic fiber outerbraid on the TT1100-OHP
cable can catch and hold a small drip or trickle of water– to ensure
sufficient wetted length to generate a leak alarm. TT1100-OHP can also
be used on floors, in drip pans, in sumps and trenches and similar flat
surface applications, however TT1000 standard water detection cable may
be better suited to flat surfaces.
important notes
When used to monitor suspended or rack mounted pipe, TT1100-OHP
sensing cables must be attached to the pipe at the lowest point where
any water leak is most likely to drip from the pipe system. This will be the
6 o'clock position on horizontal piping but other mounting locations and
techniques may be necessary if site conditions are unusual. In particular,
special consideration should be given to pipe supports, couplings, "T's",
valves and other fittings. It is the responsibility of the installer to position
the cable such that any leak will drip onto the cable.
The sensor cable cannot stop a leak. In some installations the materials
or structures beneath the pipe system may be so critical or valuable,
that a drip tray system should be considered in addition to the sensor
cable installation. TT1100-OHP is intended to alert the user that a pipe or
system is leaking but it cannot prevent collateral damage if the leak is not
contained and repaired immediately.
ADDitionAl MAteriAls requireD
Tie wraps
Supplied by installer and sized to go around the pipe
and sensor cable. Base quantity on one tie wrap per
foot (0.3 m) for horizontal run with extra wraps at
fittings.
Rags and appropriate
Use to wipe and clean bottom and side surfaces of
cleaner
pipe prior to cable installation.
optionAl MAteriAls
TT-MBC-PC
Branch connector used to connect and branch "T"
(PN 847529-000)
lines
TT-MJC-xx-PC
This jumper cable is available in various pre-cut and
terminated lengths
TT-1100-OHP-CK-PC-M/F
Connector kit used during field connections of
(PN P000001186)
TT1100-OHP bulk cable
Don't:
• Drag the cable through water, paint, solvents, oil or other contaminants.
• Install damaged or contaminated sensing cable.
• Allow the cable to become wet or contaminated after installation.
• Exceed the maximum pulling force of 100 kg (220 lb).
• Use the cable as a rope for lifting or securing any object.
• Allow tools or heavy objects to fall on cable.
• Exceed 3300 ft (1000 m) sensor cable circuit length
1 / 8

Advertisement

loading

Summary of Contents for Pentair TraceTek TT1100-OHP

  • Page 1 Description These Instructions explain the proper procedures for installing and testing TraceTek TT1100-OHP sensing cables. TT1100-OHP sensing cables are primarily intended for use on overhead piping to detect a water leak originating from a small pin hole or crack in the pipe. The wicking action of the absorptive synthetic fiber outerbraid on the TT1100-OHP cable can catch and hold a small drip or trickle of water–...
  • Page 2: Installation

    • For sumps, containment trenches, and subfloor applications, install TraceTek hold-down clips. For TraceTek TT1100-OHP series sensing cables, use 1/2- inch (13 mm) hold-down clips (TT-HDC-1/2-NA-50). • Clean the floor surface where hold-down clips will be placed so adhesive can work properly.
  • Page 3 connect, orient, install, and test each length of sensing cable in sequence 1. connect a Modular End Termination (TT-MET-PC) to the first sensing-cable length to be installed. 2. orient sensing cable so the connector used with the end termination will be the furthest away from connection to the TraceTek alarm module.
  • Page 4 complete the system 1. Install other TraceTek components (such as Modular Branching Connectors, Weighted Lengths, and Modular Jumper Cables) as called for in the system layout. Complete the sensing circuit. note: All components of the system have male or female metal connectors or both.
  • Page 5 sensing cable test procedure Method with tracetek portable text Box (ptB) End termination 1. Ensure the end termination is connected to the sensing cable. Testing a If checking several lengths of sensing cable in series (a cable cable string string), ensure they are all connected. 2.
  • Page 6 complete system connections and layout A. TT1100-OHP is available in a variety of pre-cut and terminated E. (Optional) Install jumper cables (TT-MJC-xxx-PC) as needed to lengths. Each cable has a female plastic connector on one connect sensing cable sections if they are spatially separated. end and a male plastic connector on the opposite end.
  • Page 7 initial power-up and test connect the cable to the selected instrument and test the system. TTC-1 • Apply power to the TraceTek instrument and look for a “Normal” indication. – On TTC-1, TTSIM-1A or TTSIM-2 family, there will be a green LED and no other red or yellow LEDs. (On TTSIM-1A and TTSIM-2 the green LED will flicker off every 10 seconds.) –...