7.10 Digital Outputs.

All of the fault outputs can be wired as Normally Closed or Normally Open.
(refer to Connection diagram)
7.11 System 1 Interlock Output(DO1) is activated by all/any of the following alarms:
System 1 Low Pressure
System 1 High Pressure
System 1 Sensor Fault
Mains Power failure
These are the conditions under which the boiler or chiller on System 1 must be disabled.
The fault buzzer will cycle between ON for 5 seconds and OFF for 10 seconds continuously until muted by
pressing and holding the OK button for 2 seconds.
7.12 General Fault Output(DO2) is activated by all/any of the following alarms:
Pump 1 Over Current
Pump 1 Under Current
Pump 2 Over Current
Pump 2 Under Current
Low Water
High Water
Low Glycol
System 1 Flood Protection
System 2 Flood Protection
System 1 Excessive Consumption
System 2 Excessive Consumption
System 1 Low Pressure
System 1 High Pressure
System 1 Sensor Fault
System 2 Low Pressure
System 2 High Pressure
System 2 Sensor Fault
The user may choose to disable the boiler or chiller on System 1.