Download Print this page
TemperZone ISD 250Q Installation & Maintenance

TemperZone ISD 250Q Installation & Maintenance

Ducted split system indoor units

Advertisement

Quick Links

ISD 250Q, 300Q – 470Q
Ducted Split System
Indoor Units
Fig.1 Dimensions (mm)
PROJECTION
Not to Scale
MOUNTING CENTRES
J
W
688
OPTIONAL
SPRING MTG
CENTRES
Z
K
ACCESS
PANEL
B
OVERALL
OVERALL
MODEL
A
B
C
ISD 250Q 1625
575
975
ISD 300Q 1625
575
975
ISD 390Q 1680
700
1030
ISD 470Q 2060
700
1525
Note: The manufacturer reserves the right to change specifications at any
time without notice or obligation. Certified dimensions available on request.
Fig. 2
UNIT
100 mm
APPROX.
'U' TRAP
MODEL
ISD 250Q
ISD 300Q
ISD 390Q
ISD 470Q
H
F
REFRIGERANT
CONNECTIONS
X
600
MOUNTING
STRAP
CENTRES
Y
C
ELECTRICAL
CONDUIT HOLES
D
E
A
D
E
F
G
H
300
240
1375
425
1518
300
240
1375
425
1518
310
365
1430
555
1573
310
299
1705
555
1915
VENT PIPE
100 mm
FOR LONG
APPROX.
CONDENSATE
DRAIN RUNS
50 mm
MINIMUM
OPEN
DRAIN
CORNER LOADS (kg)
W
X
Y
Z
29
35
31
25
29
35
31
25
37
41
32
35
41
50
50
41
Net
Weight
ISD 250Q 120 kg
ISD 300Q 120 kg
ISD 390Q 175 kg
ISD 470Q 182 kg
FAN ACCESS VIA
REMOVEABLE BASE
& DRAIN TRAY
ELECTRICAL
ACCESS PANEL
65
65
DRAIN 28 OD
735 OA
J
K
125
325
125
325
125
325
170
165
Condensate Drain
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
Installation &
Maintenance
GENERAL
These ISD indoor units are designed to be
coupled with their respective OSA outdoor
units. Units must be installed in
accordance with all national and local
safety codes.
Combinations
One ISD 250Q with one OSA 240RA
One ISD 250Q with one OSA 250
One ISD 300Q with one OSA 290RA
One ISD 300Q with one OSA 300
One ISD 390Q with one OSA 390
One ISD 390Q with one OSA 410RA
One ISD 470Q with one OSA 480
Options
1. Filter Box.
2. Spring Mounting Kit
3. Electric Heat Kit.
FILTER BOX (Option)
The Filter Box is installed by unscrewing
the return air spigot and replacing it with
the Filter Box's filter-integrated spigot. The
filter may be accessed from either side of
this spigot. This new spigot has a depth of
150 mm, instead of 65 mm.
ISD c/w ELECTIC HEAT OPTION
G
(Factory Fitted)
Units supplied with electric boost heat are
80
designed to conform to AS/NZS 3350.2.40
1997.
ISD 250Q–390Q: 3 x 3 kW elements
ISD 470Q: 3 x 4 kW elements
Note: Reverse Cycle systems fitted with
electric heat require an Outdoor Unit low
limit t/stat (supplied separately).
UNPACKING UNITS
In an area adjacent to the installation site
remove from the ISD unit from its carton
and examine it carefully for any damage
which may have occurred in transit. Record
any damage on the carrier's delivery
documents and refer the matter
immediately to the manufacturer's nearest
Sales Office.
INSTALLATION
Positioning & Mounting
Provide 500 mm minimum clearance to the
electrical panel. If the filter box option is to
be used, allow adequate clearance for the
two half length filters to be withdrawn from
either side of the unit.
If low noise is a critical factor in the
installation, refer to Figure 6 for noise
isolation recommendations.
It is recommended that the unit be mounted
using the spring mounting system, supplied
as an optional extra (Fig.3). This system
minimises transfer of vibration into the
building structure.

Advertisement

loading

Summary of Contents for TemperZone ISD 250Q

  • Page 1 ISD 300Q safety codes. ISD 390Q Not to Scale Combinations ISD 470Q One ISD 250Q with one OSA 240RA One ISD 250Q with one OSA 250 Weight One ISD 300Q with one OSA 290RA MOUNTING CENTRES ISD 250Q 120 kg...
  • Page 2 Pipe Connection Sizes & Type Test the air safety switch by running by the manufacturer and may cause ISD 250Q – 390Q : the fan on its lowest speed and operational problems such as poor checking for electrical heating. Remove...
  • Page 3 Fig. 5 Application Considerations Recommendations for Noise Isolation - particularly for high static installations: 1. Avoid installing units, with non-ducted return air, directly above spaces where noise is critical. 2. Use flexible connections between unit and rigid ducting. 3. Use generously sized acoustically lined ducts. 4.
  • Page 4 © temperzone limited 2006 11/06 Pamphlet No. 2682...

This manual is also suitable for:

Isd 300qIsd 390qIsd 470q