INSTALLING THE THERMOSTAT
1. Verify that the thermostat is
suitable for the area where it is to
be installed.
2. Check the line voltage and the
heat-tracing load to ensure that
the thermostat ratings are not
exceeded.
3. Mount the unit using unistrut or the Raychem universal
mounting bracket (UMB-263757) in a position that prevents
condensation from draining into the enclosure from the
connecting conduit (see diagram above).
POSITIONING THE SENSOR BULB
4. Position the bulb in the
lower quadrant of the pipe
as shown in the diagrams
to the left. Place the bulb
at least three feet from
pipe supports, valves, or
other heat sinks; protect
the capillary from kinks or
bends less than 1⁄2 inch in
radius.
WIRING
GFEPD
208-V or 240-V supply – 240-V heater
Ø
Ø
or
G
120-V supply – 120-V heater
N
Ø
277-V supply – 240-V heater
Control
thermostat
Power
G
connection
Thermostat bulb
(see "Positioning"
Braid
instructions above
for mounting details)
Heating
Cable
Figure 1. Pipe-sensing
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
thermal.info@pentair.com
Pentair and DigiTrace are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the
right to change specifications without prior notice.
© 2001-2013 Pentair.
THERMAL MANAGEMENT SOLUTIONS
Conduit
drain
Single traced
90
Heating cable
Control thermostat bulb
AT-180 tape
Double traced
Heating cable
Control thermostat bulb
AT-180 tape
GFEPD
208-V or 240-V supply
Ø
Ø
or
G
120-V supply – 120-V heater
N
Ø
277-V supply – 240-V heater
Control
thermostat
Alarm
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Figure 2. Low-temperature alarm
EUROPE, MIDDLE EAST, AFRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
thermal.info@pentair.com
EN-DigiTraceE507SLS-IM-H56913      01/13
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape,
making sure there is no air space between the bulb and pipe.
Do not overlap the bulb and heating cable with the same piece
of AT-180 tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp
(purchased separately) and install the clamp per the
instructions provided. Make sure there is no air space between
the tank wall and the bulb.
For installation on plastic tanks, contact Pentair Thermal
Management at (800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish
wiring.
8. Complete insulating. Do not turn the system on until the bulb is
covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle,
check the fluid temperature with an immersed thermostat
(best for plastic systems) or an accurate temperature indicator.
Adjust the dial setting if necessary.
GFEPD
208-V or 240-V supply
Ø
Ø
G
or
120-V supply – 120-V heater
N
Ø
277-V supply – 240-V heater
Control
thermostat
Alarm
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Figure 3. High-temperature alarm
ASIA PACIFIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2917
cn.thermal.info@pentair.com
GFEPD
120- V supply – 120-V heater or
G
N
N
N
Ø
Ø
Ø
A
B
C
A
B
C
277-V supply – 240-V heater
NC
NO
C
C
120-V or
277-V
coil
NC
NO
C
Thermostat bulb
Braid
(see "Positioning"
instructions above
Heating
for mounting details)
cable A
Heating
cable B
Heating
cable C
Figure 4. Contactor control
For switching heat-tracing loads greater than 22 A
or switching multiple heat-tracing circuits.
WWW.THERMAL.PENTAIR.COM
LATIN AMERICA
Tel: +55.11.2588.1400
Fax: +55.11.2588.1410
thermal.info@pentair.com
Control
thermostat
PN 137863
2 / 2

Advertisement

loading

This manual is also suitable for:

Digitrace amc1b