2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
areas where leakage of flammable gas may be expected.
G
places where large amounts of oil mist exist.
G
direct sunlight.
G
locations near heat sources which may affect the
G
performance of the unit.
locations where external air may enter the room directly.
G
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
locations where the remote controller will be splashed with
G
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
G
locations where high-frequency emissions are generated.
G
DO:
select an appropriate position from which every corner of the
G
room can be uniformly cooled.
select a location where the ceiling is strong enough to
G
support the weight of the unit.
WARNING
select a location which can support a load that is four times
G
the indoor unit weight.
select a location where tubing and drain pipe have the
G
shortest run to the outdoor unit.
allow room for operation and maintenance as well as
G
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
G
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the installation
instructions packed with the outdoor unit.
allow room for mounting the remote controller about 1 m off
G
the floor, in an area that is not in direct sunlight nor in the
flow of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the
ceiling is greater than 3 m.

3. HOW TO INSTALL THE INDOOR UNIT

3-1. Select the Best Location

There should not be any heat source or steam near the unit.
G
A place where air circulation in the room is good.
G
A place where drainage can be easily done.
G
A place where noise prevention is taken into consideration.
G
Do not install the unit near the door way.
G
Ensure the spaces indicated by arrows from the wall, ceiling,
G
fence or other obstacles.
Recommended installation height for indoor unit shall be at
G
least 800 mm.
Must install on a vertical wall.
G
When install electrical equipment at wooden building
G
of metal lath or wire lath, according to electrical facility
technical standard, no electrical contact between equipment
and building is allowed. Insulator must be installed in
between.
Do not install the indoor unit at outside a building. This is
G
designed for indoor installation only.
1.
The indoor unit must be within a maintenance space.
300 mm
or more
Drain Hose
ø9.52 mm
(3/8") Liquid
Refrigerant
Piping
ø15.88 mm (5/8") Gas
Refrigerant
Piping
Water Inlet
piping
[
Water Outlet
piping
Cable list:
G Power Supply cable
G Inter-unit control wiring
G Remote controller wiring
G MINI Seri-Para I/O wiring
G Other cable
G 2-way Valve cable
G Room Thermostat cable
G External Controller cable
8
300 mm
or more
300 mm or more
]
Check that all the
cables do not touch
the hot piping, etc.
Type
designation
60245 IEC
57 or heavier
cable
Optional