7-4. Detailed settings for Air-to-Water (extract)

High-spec Wired Remote Controller (CZ-RTC5)
1. Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD display.
2. Press the
or
you wish to see the next screen instantly, press the
or
button.
Select "13. Air-to-Water unit" on the LCD display and press
the
button.
Code no.
02
Mode select (TANK, A/C)
04
Heating curve function use
05
Existence of External device
06
Optional thermo sensor use
07
2-way Valve
22
Outdoor temperature using internal heater
31
Temperature for sterilization
52
ON/OFF timing of external device
ON/OFF timing of water pump for detecting the tank
53
temperature
54
External Water Pump connection
,
and
buttons
button to see each menu. If
Menu
3. Press the
you wish to see the next screen instantly, press the
or
button.
Select "Air-to-Water settings" on the LCD display and press
the
button.
4. The "Air-to-Water settings" screen appears on the LCD display.
Select the "Code no." by pressing the
button for changes.
5. Select the "Set data" by pressing the
button.
Select one of the "Set data" by pressing the
button.
Then press the
Set data
0000: No *
0001: TANK
0002: A/C
0000: No
0001: Yes *
0000: No *
0001: Yes
0000: No *
0001: R/C
0002: Remote sensor
0003: Ext. thermo
0000: Normal Open
0001: Normal Close *
-20°C ~ 25°C (* 0°C)
50°C ~ 65°C (* 55°C)
25°C ~ 65°C (* 40°C)
1~12 ×10 min.
(* 2×10 min.)
0000: No *
0001: Yes
* Default setting
22
or
button to see each menu. If
button.
Air-Conditioning
TANK mode
mode
or
or
or

Advertisement