Intruder alarm system
Service mode
1 1
System setup
System setup
Zones
3 3
Advance to the next unlearned zone with keypad
Z01 Door
keys [ ] or [7].
Name
Door
1 1
Enable the wireless zone by changing Not used
Z01 Door
loop type to any other loop type. If the system uses
Loop type
NO/DEOL
3 3
a keypad produced before 2014, an installer is
obligated to change the loop type to NO/DEOL or
Vibration.
Enter the zone address in MA_Z format, where MA
Z01 Door
is a module address in the system and Z is a zone
3 3
Address
06_1
number in the module.
Note: for wireless zones MA_1 – MA_8 the system
will automatically assign NO/DEOL loop type and
for wireless zones MA_9 – MA_16 the Vibration
loop type. Don't change the loop type of a zone!
Module address:
EXT116S - address 06 (default) or given during
the registration process;
Virtual module EXT116S address depends on the
control panel type:
P16 - address 12;
P32 - address 12 and 13;
Enter wireless detector loop (zone) ID number and
Z01 Door
Z01 Door
press the [ENT] key to start enrolling. This field may
4 4
WL det. loop (zone) ID
WL det. loop (zone) ID
201
also be used for deleting the sensor from the
module.
When enrollment has started, immediately press
Waiting for
the tamper switch for a short period of time (~1 sec)
as shown in the picture. You will feel a light click after
WL detector
pressing the switch. The tamper switch is now
activated and the detector will transmit a tamper
message.
Wireless detector successfully enrolled. No
Done
additional transmissions are needed for
confirmation.
Due to the fact that there may be changes in the passive environment after installation, it is possible to temporarily attenuate the radio frequency link during installation or
maintenance. In order to temporarily attenuate the radio frequency change the setting Attenuation as described below:
Service mode
System setup
1 1
System setup
W ireless settings
7 7
Change setting's Attenuation value to 3dB. Save
W ireless settings
changes by pressing the [ENT] key.
Normal cond.
1 1
Attenuation
Caution: Each wireless detector is supervised by a
check-in signal that is sent to the receiver at 60
W ireless settings
minutes interval. During this check-in commu-
nication the detector will receive new settings and
1 1
Attenuation
3dB
will start to work according to them. DO NOT
FORGET to change the Attenuation setting's value
W ireless settings
to Normal cond. when installation or maintenance
1 1
Attenuation
3dB
works are finished.
Please act according to your local rules and do not dispose of your unusable alarm system or its components with other household waste. This
product utilization in EU is covered by European Directive 2002/96/EC.
Page 2
ENROLLING
Wireless detector loop (zone) enrolling ID numbers
Use
Passive infrared
sensor
(PIR sensor)
Built-in
temperature
sensor
Delete detector in
a specific zone
Delete all
detectors
in a specific
wireless module
IMMUNITY TO ATTENUATION
BP1 Wireless detector
Supports
Wireless detector loop (zone) ID number
BP1
BP1
All
All
Installation manual
181
180
255
254
Rev.02/08/16_K2