Samsung AVMKH020EA4 Service Manual page 32

System air conditioner
Hide thumbs Also See for AVMKH020EA4:
Table of Contents

Advertisement

Outdoor Unit (cont.)
Outdoor Type
Model
Power Source
Mode
Performance
Horse Power
Cooling
Heating
Sound Level(Cooling/Heating)
Power
Running
Current
Power Input
Breaker (MCCB/ELB)
Compressor
Type
Model
Piston Displacement
Output
Lubricant
Refrigerant
Type
Charging
Fan
Type
Output
Air Flow Rate
Dimension
Net Weight
Shipping Weight
Net Dimension (WxHxD)
Shipping Dimension (WxHxD)
Piping
Connecting
Pipe
Piping
Limitation
Cable
Main Power (Below 20m/Over 20m)
Communication
Cooling
Operating
Temp. Range
Heating
✳ 1) Nominal cooling capacities are based on :
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 7.5m(horizontal)
✳ 2) Nominal heating capacities are based on :
- Indoor temperature : 20˚C DB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m(horizontal)
✳ 3) Noise level acquired in a dead room, so actual noise level may be different depending on the installation
conditions.
Samsung Electronics
ø, V, Hz
HP
kW
✻ 1)
Btu/h
kW
✻ 2)
Btu/h
✻ 3)
dB
Cooling
A
Heating
A
Cooling
W
Heating
W
A
-
-
cc/Rev
kW
Type
-
Charging
cc
-
kg
-
W
CMM
kg
kg
mm
mm
ø, mm
Liquid
ø, mm
Gas
ø, mm
Others
m
Max. Length
m
Max. Height
mm
2
mm
2
˚C
˚C
Product Feature and Specifications
RVMMH140EZ
1, 220-240~, 50
Heat pump
5.0
14.0
47,800
16.0
54,600
52/53
22.5
21.5
4,650
4,500
40
Digital scroll
ZRD68KC-PFZ
98.06
4.2
SONTEX 200LT
1,890
R22
6.5
Propeller
200x2
95
125
133
932x1,128x375
1,091x1,286x472
9.52
19.05
-
70
30
5.5/8.0
0.75~1.25
-5 ~ 43
-15 ~ 24
2-25

Hide quick links: