11-4-2 Outdoor unit
1. Check the discharge temperature (T-discharge) of compressor.
G If it maintains 70˚C ~ 110˚C, it is judged normal.
G
Example) Discharge Temp.: 70˚C ≤ 95˚C ≤ 110˚C
2. Check the middle temperature of condensing temperature(T-Cond).
G Check the middle temperature of condenser.
G It is normal if the temperature 5˚C ~ 20˚C over than that of outdoor(T-air. out).
G
Example) Condensing Temp.(29+5): 34˚C ≤ 45˚C ≤ (29+20) : 49˚C