11-2 Self-diagnosis by the outdoor unit error display

11-2-1 Indoor unit room temp. sensor error (open / short)
Outdoor unit display
Indoor unit display
Judgment method
Causes
indoor room temperature sensor
connecter from PCB?
Detach indoor room temperature sensor
connecter from PCB, and measure the resis-
tance value between the both terminals.
Is the resistance
value far from the
temperature table?
Restart after PCB exchange.
11-5
x x x
(x x x : Indoor unit address occurred error)
(Operation)
(Timer)
- Refer to the below judge method
- OPEN/SHORT defect of indoor temperature sensor
Is separated the
No
No
(Fan)
(Filter)
(Removing frost)
Yes
Restart after connecting a connecter to PCB.
Yes
Replace the indoor room temperature
sensor because it is defect.
Temperature
Resistance
(˚C)
(kΩ)
70
2.2
60
3.0
50
4.2
40
5.8
30
8.3
20
12.1
10
18.0
0
27.3
-10
43.0