11-2-16 Indoor unit freezing protection
Outdoor unit display
Indoor unit display
Judgment method
Causes
✳If the outdoor temperature is so low(below -5˚C) or a number of indoor unit is off simultaneously, the indoor unit can be frozen in an instant.
Check the indoor unit detected freez-
ing.
Remove the obstacles of
corresponding indoor unit and clean
the dust filter.
Error reset(KEY3)
Operate a corresponding
indoor unit.
Does operate normally the
indoor unit fan motor?
Yes
Test operation for every
room(KEY 4)
Is high/low pressure normal ?
Yes
It is completed to check the system.
Samsung Electronics
(Operation)
(Timer)
- When the temperature of indoor unit heat exchanger on cooling operation maintains
over 5 minutes below -4˚C
- Indoor fan motor defect or lock
- EEV open error
No
(Fan)
(Filter)
(Removing frost)
Is the voltage
of PCB fan motor output
terminal normal?
Yes
Replace the motor after checking
the connection wire of fan motor.
No
After checking the quantity of
refrigerant, if needed recharge
the refrigerant.
Troubleshooting
No
Restart after PCB
exchange.
11-20