Connecting a bus device to an M-Link device
The M-Link device can read the device points of a device connected to its own Modbus/RTU bus. The device
points may be physical measurement results, settings, controls etc. The read points can be brought up to Ounet
or other SCADA systems or transferred as a point transfer to another device via the TCP/IP bus. The device
whose device points are read, is added as a bus device using the OuflexTool.
4
2
5
7
7
9
1
3
6
10
1.
Open OuflexTool. Select M-Link.
2. Select "Devices"
3. Select Modbus master (SerialPort2)
4. Select "Add device".
5. If the device you want to add is on the list,
select the device.
6. Just select points from the list of points you
want to read
7. If the device cannot be found from the list,
select "New device" -> name the device -> and enter
a unique device address
8. Add the new device' s points to the points list.
Create the points for the device by right-clicking a
group in the point list.
8
9. Fill out the form data, "Point Type," "Modbus set-
tings," and "Point common settings".
10. When the desired Modbus points have been
added, select "Device" tab and then "Create" "ounet
template". The device can now be brought up to Ou-
net.