1.
FEATURES
FEATURES
Energy saving technology (ALL DC)
z
DC twin rotary compressor
High efficiency
compressor motor
Optimized refrigerant
flow design
Highly accurate parts
Peak cut operation
z
Peak cut mode (Optional parts: UTY-XWZXZ2)
Suppresses maximum capacity and performs energy-saving operation and can prevent breaker
tripping.
This function performs operation by setting a peak current value and reducing the power
consumption.
* Performance drops by reducing the power consumption preferentially.
Level 1 ... Performs operation which suppresses the power consumption to almost 0% by
stopping the compressor.
Level 2 ... Performs operation which suppresses the power consumption to 50% of the rated
power consumption value.
Level 3 ... Performs operation which suppresses the power consumption to 75% of the rated
power consumption value.
Level 4 ... Performs operation which suppresses the power consumption to the rated power
consumption value (100%).
Capacity
Setting level
W
Control
device
High install ability long piping correspondence
z
Max pipe
length
75m
Chargeless
30m
DC twin rotary compressor
Efficiency in all load regions is good.
Especially good performance from low to
medium at normal operation.
High
DC Twin Rotary compressor
Peak cut
Signal input
Max height
difference
30m
High
Compressor capacity
Time
Long piping provides an outdoor unit and indoor
unit layout margin.
- (02 - 01) -
DC fan motor
Miniaturized, low noise,
high efficiency, multi-stage
DC fan motor is mounted.