Setting Method - Fujitsu AR*G60LHTA Design & Technical Manual

Air conditioner duct type, refrigerant r410a inverter, indoor/outdoor
Hide thumbs Also See for AR*G60LHTA:
Table of Contents

Advertisement

15-1-2.

SETTING METHOD

 Stop the operation of air conditioner before this setting.
LOW NOISE MODE
LED display part
SW2
(1) Switch to "Local setting mode" by pressing [MODE] switch (SW2) for 3 seconds or more.
(2) Confirm (POWER / MODE) blinks 9 times, and press [ENTER] switch (SW4).
TEST
PUMP
POWER
ERROR
RUN
DOWN
MODE
(L1)
(L2)
Blinks
(9 times)
Sign "
" : Lights off
(3) Press [SELECT] switch (SW3), and adjust LED display as shown below. (Current setting is
displayed)
TEST
RUN
(L1)
LOW NOISE
MODE
(4) Press [ENTER] switch (SW4).
TEST
RUN
(L1)
LOW NOISE
MODE
Sign "
(5) Press [SELECT] switch (SW3), and adjust LED display as shown in below figure.
Level 1 ... Rated noise value -2dB
Level 2 ... Rated noise value -4dB
(6) Press [ENTER] switch (SW4) and fix it.
Level 1 ... Rated noise value -2dB
Level 2 ... Rated noise value -4dB
(7) Return to "Operating status display (Normal operation)" by pressing [EXIT] switch (SW5).
• In case of missing how many times [SELECT] and [ENTER] switch are pressed, restart from the beginning of
operation procedure after returning to "Operation status display (normal operation)" by pressing the [EXIT] switch
once.
SW3
SW4
SW5
LOW NOISE
PEAK CUT
(L3)
(L4)
(L5)
(L6)
(L7)
PUMP
LOW NOISE
DOWN
(L2)
(L3)
(L4)
Blink
PUMP
LOW NOISE
DOWN
(L2)
(L3)
(L4)
" : Lights on
PEAK CUT
(L5)
(L6)
(L7)
Blink
Blink
PEAK CUT
(L5)
(L6)
(L7)
- (02 - 23) -