Fujitsu AR*G60LHTA Design & Technical Manual page 58

Air conditioner duct type, refrigerant r410a inverter, indoor/outdoor
Hide thumbs Also See for AR*G60LHTA:
Table of Contents

Advertisement

FUNCTIONS
LED lamps
(1)
(2) (3) (4)
SW1
SW2
SW3
(5)
(6)
(1) POWER / MODE
(2) ERROR
(3) TEST RUN (L1)
SW4
SW5
SW6
(4) PUMP DOWN (L2)
(5) LOW NOISE MODE
(6) PEAK CUT MODE
- (02 - 22) -
Display lamp
Green
Red
Orange
Orange
Orange
(L3, L4)
Orange
(L5, L6, L7)
Switch
SW1
DIP switch
SW2
Push switch
SW3
Push switch
SW4
Push switch
SW5
Push switch
SW6
Push switch
Dip switches 1 to 4 at shipment from the factory are
set as follows.
Switch
1
2
COOL
OFF
Function or operation method
Lights on while power on Local setting in
outdoor unit or error code is displayed with
blink.
Blinks during abnormal air-conditioner
operation.
Lights on during test operation.
Lights on during pump down operation.
Lights on during "Low noise" function
when local setting is activated.
(Lighting pattern of L3 and L4 indicates
low noise level) ðSee page (02-23).
Lights on during "Peak cut" function when
local setting is activated.(Lighting pattern
of L5, L6 and L7 indicates peak cut level)
ð See page (02-24).
Function or operation method
For selecting cooling or heating during
test operation.
Positions 2 to 4 of Dip switch are not used.
To switch between "Local setting" and
"Error code display".
To switch between the individual "Local
settings" and the "Error code displays".
To fix the individual "Local settings" and
the "Error code displays".
EXIT
To start the pump down operation.
3
4
OFF
OFF