Measuring transducer MI 436 is CE-marked according to the LV-directive and EMC- directive for housing and light industry, which normally covers the most common use of the measuring transducer.
The ease of programmability of transducer is an important feature in the provision of cost effective system control. Systems can be easily changed or expanded as required. User's Manual MI 436...
3) – Qualified person only following measuring values: • True RMS input voltage (phase to neutral and phase to phase) • %THD Picture 1: Block diagram User's Manual MI 436...
• Programmable ratings: Measuring range limit values: 0…50 V to 0…500 V • Nominal frequency f 50/60 Hz • Frequency range: 45…65 Hz • Consumption: / 3 MΩ • Overload capacity: according to EN 60688: 1992 User's Manual MI 436...
5) – To calculate intrinsic error, see chapter intrinsic-error (for analogue • Rated voltage (Ur): 24…300 V DC outputs) on this page. 40…276 V AC • Frequency range: 40…70 Hz • Power consumption: < 3 VA User's Manual MI 436...
0.14 mm except between communication terminals and output terminals, 2 kV rms for 1 minute • Transmission mode: Asynchronous • Message format: MODBUS RTU • Data rate (very high speed): 1,200 to 115,200 bits/s • RS485 connections User's Manual MI 436...
5. MOUNTING load – 3u MI 436 is appropriate for rail mounting according to SIST EN 60715. On picture below you can see rail mounting. Picture 3: Rail mounting of the transducer User's Manual MI 436...
(Picture 7): One label at the front of housing (Picture 6): Picture 7: Example of label for transducer with bent characteristic Picture 6: Example of label for transducer with linear characteristic User's Manual MI 436...
Page 14
Printed in Slovenia • Subject to change without notice • Version 01 / avg. 2006...