Control Devices
5. Control Mode Selector (DS2)
The following four patterns of control mode can be set.
Control Mode Individual
Content
Operation/stop is
controlled by both unified
ON/OFF controller and
remote controller.
DS2 Setting
(Factory set)
Note:
 "" Indicates the position of switches.
 Set control mode before turning power supply ON.
 When used in conjunction with central remote controller, the control modes of the central remote controller has the
priority.
6. Forced Reset Switch (SS1)
When changing the setting of the connector for setting master controller, etc., you can reset simply by setting it to the
reset side once and returning to the normal side, without turning the power OFF.
(For normal operation, set the switch to the normal side.)
46
Centralized
Timer Operation Possible by
Remote Controller
After operated by unified
When used in conjunction
ON/OFF controller,
with schedule timer,
operation/stop is freely
operation/stop is controlled
controlled by remote
freely by remote controller
controller until stopped by
during the set time but
unified ON/OFF controller.
operation is not available
when schedule timer is ON.
EDUS391000-C
ON/OFF Control Impossible
by Remote Controller
Operation/stop is controlled
by unified ON/OFF controller
only. (This unit can not be
operated/stopped by remote
controller.)
Controls