9 Settings
Domestic water storage tank
Type of charging
1: Recharging | 2: Full charging | 3: Full charging legio | 4: Full charg 1st time
day | 5: Full charg 1st time legio
Switching diff
Charging time limitation
Discharging protection
0: Off | 1: Always | 2: Automatically
Discharg protec after charg
Off | On
Charging temp max
Recooling temp
Recooling collector
0: Off | 1: Summer | 2: Always
El imm heater optg mode
1: Substitute | 2: Summer | 3: Always
El immersion heater release
1: 24h/day | 2: DHW release | 3: Time program 4/DHW
El immersion heater control
1: External thermostat | 2: DHW sensor
Automatic push
Off | On
Excess heat draw
Off | On
With buffer
No | Yes
With prim contr/system pump
No | Yes
With solar integration
No | Yes
Pump speed min
Pump speed max
Speed Xp
Speed Tn
Speed Tv
Transfer strategy
0: Off | 1: Always | 2: DHW release
Interm circ boost recharging
Intermediate circuit boost
Excess interm circ temp max
Flow setp compensation delay
Flow setp compensation Xp
Flow setp compensation Tn
Flow setp compensation Tv
Full charging with B36
No | Yes
Min start temp diff Q33
Excess interm circ temp del
(1) Parameters depend on the hydraulic System!
Configuration
Heating circuit 1
Off | On
Heating circuit 2
Off | On
Heating circuit 3
Off | On
70
Paramount five 30 – 115
(1)
Prog. no.
Level
Standard value
5022
E
Full charging
5024
E
4 °C
5030
E
120 min
5040
E
Automatically
5042
Off
5050
E
69 °C
5055
E
80 °C
5057
E
Off
5060
E
Substitute
5061
E
DHW release
5062
E
DHW sensor
5070
E
On
5085
E
On
5090
E
Yes
5092
E
Yes
5093
E
Yes
5101
E
0 %
5102
E
100 %
5103
E
15 °C
5104
E
60 s
5105
E
5 s
5130
E
Always
5139
E
5 °C
5140
E
2 °C
5141
E
2 °C
5142
E
30 s
5143
E
50 °C
5144
E
30 s
5145
E
30 s
5146
E
No
5148
E
-3 °C
5151
E
30 s
Prog. no.
Level
Standard value
5710
C
On
5715
C
Off
5721
C
Off
7703046 - 01 - 23072018