7 Aerial Installation
Refit the previously removed Aerial Fly
Lead connection.
Fit the Aerial to the BNC connection at
the top of the unit and twist clockwise to
secure into position.
Fit the Aerial Anti-Tamper Shroud over
the aerial.
Secure the shroud, by tightening the
two
Thumb
Nuts
onto
bottom of the Aerial Shroud as
shown.
Note: If fitting a Remote Aerial
to
the
RNC,
replace
standard Aerial shown.
Refer to the 'Radio Network
Communicator
Installation
Details
sheet'
(TSD105)
additional information on fitting
remote aerials.
9 Configuration
Programming is only necessary if the RNC, when powered
displays 'Unprogrammed'.
The RNC's programming is configured within the menu structure
of the RNC.
Refer to the 'RNC Quick Start Guide' (TSD106)
for programming information. These details
can also be found on the RNC lid.
If the RNC is displaying a fault, recheck wiring
then refer to the 'RNC Programming Manual'
(MK137) for full details.
(Free to download from www.emsgroup.co.uk)
Specification
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
IP Rating
IP54
Operating
Voltage
75mA @24Vdc
Operating
Frequency
458MHz
Output
Transmitter
Power
500mW
Dimensions
156mm (W) 228mm (H) 48mm (D)
Weight
0.65kg
Application
Indoor Use Only
the
the
for
8 Connection Wiring
Cables should only be passed via the access points available.
Flame retardant cable glands should be used.
DO NOT leave excess cable in the RNC.
DO NOT earth the enclosure box.
POWER IN
24Vdc
-
+
To
Control
Panel
-
+
AUX
24Vdc
Once all connections are made, apply power to the Control
Panel.
10 Close RNC
Refit the RNC Lid to complete the installation.
Regulatory Information
Manufacturer
Year of
manufacture
Complies with
European Union
directives
Page 2 of 2
To
Control
Panel
Fire Control Panel
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
See devices serial number label
EN300-220
EN301-489
EN60950
Hereby, EMS declares that the radio equipment type
FireCell
RNC
is
in
compliance
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address: www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be disposed
of as unsorted municipal waste in the European
Union. For proper recycling, return this product to
your local supplier upon purchase of equivalent new
equipment, or dispose of it at designated collection
points.
For more information see www.recyclethis.info
RS485
RS485
OUT
IN
+
-
+
-
+ -
+ -
NET
NET
OUT
IN
with
Directive

Advertisement

loading

This manual is also suitable for:

Firecell fc-tak-438-001