Installation steps
Only qualified licensed installers shall perform this installation. Prior to commencing, ensure all power sources, power and data cables
are de-energized and isolated (touch safe)
1.
Ensure mains supply input for DC power supply, PoE Ethernet network and DyNet network are all de-energized before terminating.
2.
Select an appropriate mounting location indoors only following recommendations from the Mounting Location section. Mount the device and power supply as required by
local wiring rules. Use Philips EWAC mounting accessories as required for surface or rack installations. To mount the device on DIN rail or mounting plate, slide the two
DIN clips at the bottom of the device downwards with a screwdriver. Click the device onto the rail and slide the clips back into place. This device is approved for plenum
installation.
3.
External PS and DyNet only:
a.
Strip-off around 30 mm of cables outer insulation jacket
b.
Neatly wrap the stripped area of cable with insulating tape leaving approximately 20mm of inner wires free for termination
c.
External PS option only: Strip and terminate power supply Class 2 output wires to the SUPPLY IN terminals of EWAC. Ensure correct polarity.
d.
Strip and terminate DyNet port wires as required. Ensure correct connection.
e.
Where used, AUX dry contact input wiring cable length should be less than 10m (30 feet). Use of twisted pair wires is recommended to minimize noise
coupling
Ensure wires are segregated and fully inserted with no exposed copper outside terminals to prevent shorts.
All Class 2 / SELV cables shall be segregated from Class 1 wiring per local wiring code.
To minimize noise coupling on long parallel cable runs, it's recommended to provide at least 300mm (1 foot) separation between data and mains cables (except for
installations with steel conduits used).
4.
Connect Ethernet, Supply and Data cables as required.
5.
Energize supply and network and check for correct operation. If programming is required use a PC with EnvisionProject Software.
FCC/IC compliance statement
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license‐ exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Any changes or modifications not expressly approved
by Philips could void the user's authority to operate this equipment. This product is intended for commercial use only.
DÉCLARATION DE CONFORMITÉ À LA FCC/IC
Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États‐ Unis et d'Industrie Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est
assujetti aux deux conditions suivantes: (1) Ce dispositive ne doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris le brouillage pouvant entraîner un mauvais
fonctionnement. Tous les changements ou modifications non expressément approuvés par Philips, sont susceptibles d'annuler le droit de l'utilisateur à se servir de cet équipement. Ce produit est
exclusivement destiné à un usage commercial.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate
the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the
dealer or an experienced radio/TV technician for help.
Network connection
Product specifications:
Supply options:
Communication Ports
Supported Ethernet Protocols
Supported ZigBee protocols
Input / Output Terminals
Operating Environment
Transport and Storage Conditions
Philips Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road, Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
Option 1: PoE, IEEE 802.3at Class 0 Type 2, 37-57Vdc, 8W max
Option 2: Commercial grade Power Supply 12/24Vdc SELV/Class 2, 100mA max plus DyNet load
@12Vdc / 60mA max plus DyNet load @24Vdc
Option 3: from DyNet network: 100mA max@12Vdc / 60mA max@24Vdc SELV/Class 2
Contribution to DyNet network: max. 120mA load @ 12Vdc (Option 1) or
Allowed supply ripple (Option 2 & 3): 1Vpp max
Power consumption: max.2W (excluding DyNet and ILB)
10/100BaseT Ethernet port, RS485 DyNet serial port, ILB port, Zigbee port, Infra-RED RC5
EnvisonIP/DyNet2, TFTP, xCLIP, IPv6
ZHA/ZLO, Green Power
Ethernet PoE: RJ45
External Power Supply: 2-pole 5mm pluggable header, 1 x 2.5mmsq conductor size
DyNet: 6-pole 5mm pluggable header, 1 x 2.5mmsq conductor size
ILB: RJ10
User Controls
Service / Pairing Push Button, Multifunction status LED (RGB), RC5 IR receiver, 100/100BT status LED
Compliance
CE, RCM, UL, FCC, ICES
-5C to +50C ( 23F to 122F), 0-90% RH non-condensing
-25C to +70 C ( -13F to 158F), 0-90% RH non-condensing
Construction
Low Profile Din Rail Polycarbonate (6 unit), UL94-V0 rated
Dimensions
H 97mm x W 110mm x D 39mm (pluggable terminal connectors will add 9mm to the total height)
Weight
Packed weight 0.23kg
EWAC Rev F.docx. Specifications subject to change without notice.
Email:
dynalite.info@philips.com
DyNet Network
voltage equal to external Power Supply output (Option 2)