INSTALLATION
3. Turn the key around and place it over the opposite
holes. The tab on the bottom fits into the larger hole, and the
screw fits into the smaller hole. Make sure the arrow on the
key points in the direction of the air flow (downstream).
4. Tighten the screw into the new hole.
5. Insert the electronic cell. The ionizer section will
now be on the air-entering (upstream) side of the cabinet.
ATTACH CELL HANDLE(S)
The cell handles are attached to the packing insert in-
side the access door. They must be installed on the end of
the cell closest to the access door. To install:
1. Orient the cell as it will be when installed. The gray
contact board must be up and the airflow arrow stamped
into the cell must point downstream.
2. Hold the handle sideways and insert the solid tab on
the back of the handle into the slot in the cell. Turn the
handle 90 degrees clockwise to align the divided tab with
the square hole. See Fig. 13.
Fig. 13—Install handle on end of cell closest to
access door.
3. Insert the divided tab into the square hole.
4. Fold up the wedge and insert it into the divided tab to
lock the handle in place. If necessary, press with a blunt
instrument like the end of a pliers.
REASSEMBLE AIR CLEANER
Insert the electronic cell with the gray contact board up
and the airflow arrow pointing downstream. If the cell does
not slide easily into the cabinet, check the orientation of
the cell key.
Insert the prefilter on the upstream side of the cabinet in
the guide provided.
68-0137B—2
the door into the slot in the cabinet, then swing it closed and
press into place. The door must be firmly in place or the air
cleaner will not operate.
COMPLETE WIRING
voltage and frequency outlet. See Fig. 14 for internal sche-
matic. The air cleaner will operate properly with any fan
when wired with conduit or plugged in.
NOTE: To reduce the risk of electric shock, this product
ROTATE 90
DEGREES
with conduit.
FOLD TAB
TO LOCK
HANDLE
IN PLACE
the power box and the (2) screws from the sides of the
power box. See Fig. 15.
M6047
connect the line cord leads to the power box wiring.
grounding screw on the wiring compartment barrier.
access door) in the hole left by the power cord.
wire nuts. See Fig. 16. Secure ground connection to the
green ground screw on the wiring compartment barrier.
10
Replace the access door. Insert the tab on the bottom of
!
WARNING
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY.
Do not use an extension cord.
• All wiring must comply with local codes and ordinances.
• The line voltage power source must match the volt-
age and frequency printed on the label inside the
access door.
Plug the electronic air cleaner directly into the correct
has a grounding type plug that has a third (grounding)
pin. This plug will only fit into a grounding type power
outlet. If the plug does not fit into the outlet, contact a
qualified electrician to install the proper outlet. Do not
change the plug in any way.
Alternatively, the electronic air cleaner can be wired
1. Open access door.
2. Remove and retain the (2) screws from the front of
3. In the power box, remove and retain (2) wire nuts that
4. Remove the power cord green lead from the green
5. Remove the power cord and the strain relief.
6. Install plug (provided with packing material inside
7. Attach conduit through a power box side knockout.
8. Wire the air cleaner directly to line voltage using
9. Replace power supply cover and access door.