Designs; Control Room Housing Unit For Rail Mounting; Control Room Housing Unit For Block Mounting; Field Mount Housing - ABB TEIP11 Operating Instruction

I/p signal converter
Hide thumbs Also See for TEIP11:
Table of Contents

Advertisement

3.2

Designs

1
4
Fig. 2

1 Control room housing unit for rail mounting

2 Control room housing unit for block mounting

3 Plastic field housing unit
4 Aluminum or stainless steel field housing unit
3.2.1
Control room housing unit for rail mounting
The control room housing unit for rail mounting is the most
user-friendly and lowest priced model in the signal converter
line.
A mounting base that is compatible with all commercially
available EN rails is used for installation.
The housing unit with plastic cap has an IP 20 protection
class.
8 42/18-46-EN Rev. L | TEIP11, TEIP11-PS
2
3
M10350
3.2.2
Control room housing unit for block mounting
The control room housing unit for block mounting enables you
to install a number of converters in a small space. This design
features central air supply via connection block and stop
valves in the air connectors of the integrated signal converter.
A maximum of 4 signal converters can be fitted on the
connection blocks required for block mounting. If necessary, 2
or 3 (or max. 4) connection blocks can be connected to each
other to create block units of 4-8-12-16 signal converters.
Stop valves allow you to mount or remove individual
converters during operation.
3.2.3

Field mount housing

The field housing unit is designed for installation onsite or in
the field. Housing units are available in the following models
(and protection classes): plastic (IP 54), aluminum (IP 65) and
stainless steel (IP 65). The housing units are suitable for wall
mounting and 2" pipe mounting.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Teip11-ps

Table of Contents