EMS FireCell FC-555-024 Installation Manual page 2

24vdc radio cluster communicator (rcc)

Advertisement

7 Connection Wiring
Power cables should only be passed via the access points
available.
Flame retardant cable glands should be used.
DO NOT leave excess cable in the RCC.
RF1
RF2
RESET
HEALTHY
FAULT
POWER
FAULT
SYS FAULT
RADIO CLUSTER COMMUNICATOR
BACK
LOGON
POWER 1
Figure 9
+
-
OK
9 Configuration
The RCC's programming and loop address are configured within
the menu structure of the Radio Hub.
Refer to the
programming manual (Doc Ref: MK98) for full
programming information.
Specification
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
IP Rating
IP54
Operating Voltage
17 to 28Vdc
Power Requirements 17mA @ 24Vdc
Operating Frequency 868MHz
Output Transmitter
Power
Auto adjusting 0 - 14 dBm (0 - 25 mW)
Dimensions
270mm (W) 205mm (H) 75mm (D)
Weight
0.95kg
Application
Indoor use only
©2018 EMS Ltd. All rights reserved
POWER 2
+
-
OK
CONN3
0V
+V
0V
+V
CONN4
Free to download from
www.emsgroup.co.uk
8 Applying Power
Apply power to the power supply. The normal LED states for the
RCC are as below:
Healthy LED - Green LED will be on.
Fault LED - Yellow LED will be off.
Sys Fault LED - Yellow LED will be off.
Power 1 LED - Green LED will be on.
TX
Power 2 LED - Green LED will be on.
PRIMARY
FUSE F1
1ATH
CONN1
250V
HRC
L N
HEALTHY
CONN3
DO NOT
0v
ADJUST VR1
+v
PLK1 PLK2
0v
+v
BATTERY FUSE
3.15AF F2
CONN4
PL1
FAULT RELAY
PL2
CONN5
Temp
LOOP 1
IN OUT IN OUT
10 Close RCC
Ensure that the RCC PCB is correctly inserted and the PCB
retaining screws are refitted.
Refit the RCC lid, ensuring LEDs are not damaged by the light
pipe when refitting.
Regulatory Information
Manufacturer
Year of manufacture
Certification
Certification body
CPR Certificate DOP
Approved to
European Union
directives
Page 2 of 2
RF1
RX
RESET
RESET
FAULT
HEALTHY
FAULT
SYS FAULT
SYS
FAULT
POWER 1
+
-
LOOP 2
IN OUT IN OUT
-
-
-
-
POWER
FAULT
RADIO CLUSTER COMMUNICATOR
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
See devices serial number label
12
0359
0359-CPR-0046
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems. Part 25: Components using radio links.
EMS declares that the radio equipment type FireCell
24Vdc
RCC
is
in
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address: www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products
marked
with
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
RF2
RF1
RF2
BACK
LOGON
POWER 2
Figure 9
+
-
OK
OK
compliance
with
Directive
this
symbol
cannot
be
TSD054 Iss 8 05/09/2018