Flash Codes
Various flash codes are utilized by the unit control board (UCB)
to aid in troubleshooting. Flash codes are distinguished by the
short on and off cycle used (approximately 200ms on and
200ms off). To show normal operation, the control board
flashes a 1 second on, 1 second off "heartbeat" during normal
operation. This is to verify that the UCB is functioning correctly.
Do not confuse this with an error flash code. To prevent
confusion, a 1-flash, flash code is not used.
Alarm condition codes are flashed on the UCB lower left Red
LED, See Figure 36. While the alarm code is being flashed, it
will also be shown by the other LEDs: lit continuously while the
alarm is being flashed. The total of the continuously lit LEDs
Table 28: Unit Control Board Flash Codes
Flash Code
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Control waiting ASCD
3 Flashes
HPS1 Compressor Lockout
4 Flashes
HPS2 Compressor Lockout
5 Flashes
LPS1 Compressor Lockout
6 Flashes
LPS2 Compressor Lockout
7 Flashes
FS1 Compressor Lockout
8 Flashes
FS2 Compressor Lockout
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
Compressors locked out because the Economizer is using free
11 Flashes
1
Cooling
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
13 Flashes
Compressor Held Off due to Low Voltage
14 Flashes
EEPROM Storage Failure
OFF
No Power or Control Failure
1. Non-alarm condition.
60
Description
1
1
equates to the number of flashes, and is shown in the table.
Pressing and releasing the LAST ERROR button on the UCB
can check the alarm history. The UCB will cycle through the last
five (5) alarms, most recent to oldest, separating each alarm
flash code by approximately 2 seconds. In all cases, a flashing
Green LED will be used to indicate non-alarm condition.
In some cases, it may be necessary to "zero" the ASCD for the
compressors in order to perform troubleshooting. To reset all
ASCDs for one cycle, press and release the UCB TEST/
RESET button once.
Flash codes that do and do not represent alarms are listed in
Table 28.
Green
Red
LED
LED
16
8
-
-
Flashing
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
1
Flashing
On
Flashing
On
Off
On
Flashing
On
Off
On
Off
Off
Red
Red
LED
LED
4
2
-
-
-
-
-
-
Off
On
Off
On
On
Off
On
Off
On
On
On
On
Off
Off
Off
Off
Off
On
Off
On
On
Off
On
Off
On
On
Off
Off
Johnson Controls Unitary Products
Red
LED
1
-
-
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Off

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zj090Zj102Zj120Zj150

Table of Contents