Omega iDR Quick Start page 2

I series, monitor, limit alarm din rail temperature & process

Advertisement

This Quick Start Reference provides information
START HERE
on setting up your instrument for basic operation.
The latest complete Communication and Operational
Manual as well as free Software are available at
www.omega.com/specs/iseries or on the CD-ROM
enclosed with your shipment.
SAFETY CONSIDERATION
This device is marked with the international
Caution symbol.
The instrument is protected in accordance with
EN 61010-1:2001, electrical safety requirements for
electrical equipment for measurement, control and
laboratory. Remember that the unit has no power-on switch.
Building installation should include a switch or circuit-breaker
that must be compliant to IEC 947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on
the side of the instrument housing.
• Always disconnect power before changing signal and
power connections.
• Do not use this instrument on a work bench without
its case for safety reasons.
• Do not operate this instrument in flammable or
explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the
instrument if EMC problems persist.
MOUNTING
To install unit onto DIN Rail:
1) Tilt unit, position mounting slot onto DIN Rail, as shown.
2) Push unit towards DIN Rail and it will snap into place.
To remove unit from DIN Rail:
1) Insert flat screw-driver into tab and push downwards.
2) Unit will detach from DIN Rail.
DIMENSIONS
-EI / -C4EI
STANDARD
WIRING
Wire the instrument according to the figure shown below.
Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow
all instructions and warnings may result in injury!
Output 1 and 2 are for -AL Alarm Option only.
Connect the main power connections as shown in the figure below.
* See Specification Section
FUSE
Connector Output Type For 115Vac For 230Vac
FUSE 1
Output 1
Relay
3 A(T)
3 A(T)
FUSE 2
Output 2
Relay
3 A(T)
3 A(T)
FUSE 3
Power
N/A
100 mA(T)
100 mA(T) 100 mA(T)
FUSE 4
Power
N/A
N/A
N/A
CONFIGURATION
The following steps for configuring your device are
explained by using the optional Remote Programmer
Display (iDRP), you may also configure your device
through the Networking or Communication option
(-C24, -C4EI or -EI).
MENU Mode:
Flashing display in MENU Mode means you can make your
selection by pressing b button. If the flashing display is not
a four digit value, pressing c button will always direct the
instrument one step backward of the top menu item. The
second push on the c button will reset the instrument
except after the setpoint and the alarms, that will go to the
RUN Mode without resetting the instrument. The a button
will always sequence the instrument thru the menu items.
The d button has two functions:
1. To save a selected flashing display
2. To direct the instrument to the next submenu level
RUN Mode:
b
causes the display to flash the PEAK with the
corresponding value. Press again to go back to RUN
Mode.
c
causes the display to flash VALLEY with the
corresponding value. Press again to go back to RUN
Mode.
d
causes flashing PEAK or VALLEY to reset corresponding
values. Press
one more time to go back to RUN Mode.
d
FLOW CHART
DC
-
-
400 mA(T)
_____
Underline denotes factory default setup
OPERATION - (For Thermocouple Input)
Step 1. Apply Power to the Instrument
When your device is first powered up it will display the
ambient temperature (assume 75°F).
Step 2. Enter Setpoint 1 Menu
Press
a
one time from run mode to get to SP1 Setpoint 1.
Step 3. Enter the Setpoint 1 Value Submenu
Press
d
. Display shows the previous selection of Setpoint 1.
Step 4. Change the Setpoint 1 Value
Press
or
until desired value is displayed.
b
c
Step 5. Store the Setpoint 1 Value
Set the Setpoint 1 to 10 degree higher than Process value
(SP1 = 85) and press
to store, display flashes STRD
d
message and advances to SP2 Setpoint 2 Menu.
Step 6. Store the Setpoint 2 Value
Repeat steps 3 and 4. Set the Setpoint 2 to 5 degree higher
than Process value (SP2 = 80) and press
d
to store,
display flashes STRD message and advances to CNFG
Configuration Menu.
Step 7. Enter the Input Type Menu
to enter INPT Input Type Menu.
Press
d
Step 8. Enter to the submenu items of Input Menu
Press
d
to display Input: Process, RTD or Thermocouple.
If flashing T.ç is displayed press
a
and proceed to Step 11.
Step 9. Scroll through available selection of Input Menu
Press
until a flashing T.ç for Thermocouple is displayed.
b
Step 10. Enter to the Thermocouple Input Submenu
Press
d
to store Thermocouple Input. The display will stop
flashing and show the top menu for Thermocouple types. If
you press
a
controller will step to next menu item (Skip to Step 14).