Omega iDR Quick Start

I series, monitor, limit alarm din rail temperature & process

Advertisement

Quick Links

Step 11. Enter to the Thermocouple Type Input Submenu
Press
to display flashing, previously selected Thermocouple
d
type.
Step 12. Scroll through available selection of TC types
Press
to sequence thru flashing Thermocouple types,
b
(select k -for type "K" CHROMEGA
®
/ALOMEGA
®
)
J K T E N DIN J
R S B C - TC types
J k t E N
dN J
R S b C - Display
Step 13. Store TC type
After you have selected the Thermocouple type press
to
d
store your selection, the instrument automatically advances
to the next menu item.
Step 14. Enter to Reading Configuration Menu
The display shows RDG Reading Configuration, which is the
top menu for 4 submenus: Decimal Point, Degree Units,
Filter Constant and Input/Reading Submenus.
Step 15. Enter to Decimal Point Submenu
to show DEC Decimal Point.
Press
d
Step 16. Display the Decimal Point position
Press
again to display the flashing Decimal Point position.
d
Step 17. Select the Decimal Point position
to select FFF.F Decimal Point position.
Press
b
Step 18. Store selected Decimal Point position
By pressing
momentarily the Decimal Point position will
d
be stored and the instrument will go to the next menu item.
Step 19. Enter to Temperature Unit Submenu
Display shows TEMP Temperature Unit.
Step 20. Display available Temperature Units
to display the flashing Degree °F or °C .
Press
d
Step 21. Scroll through Temperature Units selection
to select °F Degree.
Press
b
Step 22. Store the Temperature Unit
Press
to display momentarily that the Degree Unit has
d
been stored and the instrument will go automatically to the
next menu item.
Step 23. Enter the Filter Constant Submenu
Display shows FLTR Filter Constant Submenu.
Step 24. Display the Filter Constant Value Submenu
Press
to display the flashing, previously selected Filter
d
Constant.
Step 25. Scroll through available Filter Constants
to sequence thru Filter Constants 0001 , 0002 ,
Press
b
0004 , 0008 , 0016 , 0032 , 0064 and 0128 .
Step 26. Store the Filter Constant
momentarily to store 0004 Filter Constant and the
Press
d
instrument will automatically go to the next menu item.
Step 27. Enter Alarm 1 Menu
The display will show ALR1 the top menu for Alarm 1. In the
following steps we are going to enable Alarm 1, Deviation,
Unlatch, Normally Open, Active Above, Enable at power on
and +2°F High Alarm i.e. Process Value > Setpoint 1 Value
+2°F will activate Alarm 1.
Step 28. Enter Alarm 1 Enable/Disable Submenu
to display flashing DSBL / ENBL .
Press
d
Step 29. Enable Alarm 1 Submenu
If flashing ENBL is displayed, press
, if DSBL is displayed,
a
until ENBL is displayed, then press
press
to store and
b
d
go to the next menu item.
Step 30. Select the Deviation Control Type Submenu
. If flashing _DEV Deviation is displayed press
Press
,
d
a
until flashing _DEV is shown. Now
otherwise press
b
press
to store and go to next menu item.
d
Step 31. Select the Latched Type Submenu
. If flashing UNLT Unlatched is displayed press
Press
,
d
a
until UNLT is displayed.
otherwise press
b
Press
to store and advance to next menu item.
d
Step 32. Select the Normally Open Type of Contact
Closure Submenu
. If flashing N.o. Normally Open is displayed,
Press
d
until N.o. is displayed. Press
press
, otherwise press
a
b
d
to store and advance to next menu item.
Step 33. Select the Above Type of Active Submenu
. If flashing ABoV Above is displayed, press
Press
,
d
a
until ABoV is displayed. Press
otherwise press
to store
b
d
and advance to next menu item.
Step 34. Enable Alarm 1 at Power On ( A.P.oN )
. If flashing ENBL is displayed, press
Press
, otherwise
d
a
until ENBL is displayed. Press
press
to store and
b
d
advance to next menu item.
Step 35. Enter Alarm 1 High Submenu
twice to skip ALR.L Alarm 1 Low value. ALR.L is
Press
a
for below & ALR.H for above.
Step 36. Set the Alarm 1 High value ( ALR.H )
Press
. Press
or
until value to set the display to
d
b
c
002.0 . Press
to save.
d
Step 37. Enter the Alarm 2 Menu
The display will show ALR2 the top menu for Alarm 2.
Repeat steps from 28 to 36 to set for Alarm 2 the same
conditions as for Alarm 1.
Step 38. Configuration of Display Color Selection
until the COLR Display Color Selection Menu
Press
a
appears on the Display. Configure COLR as N.CLR / GRN
(green), 1.CLR / RED (red), 2.CLR / AMBR (amber). Please
refer to the operator’s manual if needed.
Step 39. Run a Test
Press
until reset the controller and return to RUN Mode
a
to display 075.0 (Ambient Temperature). Now you are
ready to observe temperature as it rises 10°F higher than
displayed. Touch the tip of the Thermocouple to raise the
temperature above the Alarm 2 High value 082.0 , and AL2
will turn on, and Display Color will change from Green to
Amber. Continue touching the tip to raise the temperature
above the Alarm 1 High value 087.0 and Display Color will
change from Amber to Red.
SPECIFICATION
Output 1
:
Relay 250 Vac @ 3 A Resistive Load,
Accuracy:
SSR, Pulse
+0.5°C temp;
Output 2
:
0.03% rdg. process typical
Relay 250 Vac @ 3 A Resistive Load,
Resolution:
SSR, Pulse
1°/0.1°; 10 µV process
Only with -AL option
Temperature Stability:
Options: Communication
0.04°C/°C RTD;
RS-232 / RS-485 or 10BaseT
0.05°C/°C TC @ 25°C (77°F);
or Excitation: 24 Vdc @ 25 mA
50 ppm/°C process
EXC. not available for Low Power Option
iDRP Remote Programmer/Display Option:
Line Voltage/Power:
4-digit, 9-segment LED 21 mm (0.83"),
90 - 240 Vac ±10%, 50 - 400 Hz*,
48H x 96W x 39D (1.89 x 3.78 x 1.55”),
or 110-375 Vdc, 4W
159g (0.35lbs). Red, green, and amber
* No CE compliance above 60 Hz
Low Voltage Power Option:
programmable colors for process
12 - 36 Vdc, 3 W**
variable, setpoint and temperature units.
** Units can be powered safely with 24 Vac
Input Types:
but No Certification for CE/UL are claimed.
Thermocouple, RTD, Analog Voltage
Dimensions:
and Current
Standard Unit iDR:
TC: (ITS 90)
92.5H x 125.2D x 24.9mm W
J, K, T, E, R, S, B, C, N, L
(3.64 x 4.93 x 0.98”); 181 g (0.4 lb)
RTD: (ITS 68)
Ethernet Unit iDR-EI/C4EI:
100/500/1000 ohm Pt sensor
92.5H x 125.2D x 39.8mm W
2-, 3-, or 4-wire; 0.00385 or 0.00392
(3.64 x 4.93 x 1.55”); 204 g (0.45 lb)
curve
Approvals:
Voltage:
UL, C-UL, CE per EN 61010-1:2001
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc
Current:
0 to 20 mA (4 to 20 mA)
WARNING: These products are not designed for use in, and should not be used for, patient-
connected applications.
This device is marked with the international caution symbol.
It is important to read the
Setup Guide before installing or commissioning this device, as the guide contains important
information relating to safety and EMC.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OEMGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc.
accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TRADEMARK NOTICE:
®
®
omega.com
®
,
,
and
are Trademarks of
,
®
OMEGA ENGINEERING, INC.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will
extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is
returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will
issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA,
if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply
to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing,
operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit
shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive
corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to
contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA
warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO
OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED,
EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION
OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with
respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or
otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event
shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications
or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,
used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic
WARRANTY /DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless
from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY RETURNS, please have the
FOR NON-WARRANTY REPAIRS, consult OMEGA for
following information available BEFORE
current repair charges. Have the following information
contacting OMEGA:
available BEFORE contacting OMEGA:
1.
Purchase Order number under which the product
1.
Purchase Order number to cover the COST of the
was PURCHASED,
repair,
2.
Model and serial number of the product under
2.
Model and serial number of product, and
warranty, and
3.
Repair instructions and/or specific problems
3.
Repair instructions and/or specific problems
relative to the product.
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without
the prior written consent of OMEGA ENGINEERING, INC.
PATENT AND TRADEMARK NOTICE: This product is covered by one or more of the following patents: U.S. Pat.
No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / GERMANY DE
41 34398 C2 / SPAIN 2039150; 2048066 / UK Patent No. GB2 249 837; GB2 248 954 / FRANCE BREVET NO. 91
12756. The “Meter Bezel Design” is a trademark of Newport Electronics, Inc. USED UNDER LICENSE. Other U.S.
and International Patents pending or applied for.
MQS3848/0206
MADE IN
USA
iDR Monitor
iDR-AL Limit Alarm
DIN Rail Temperature & Process
®
®
®
OMEGAnet
On-Line Service
Internet e-mail
www.omega.com
info@omega.com
Servicing North America:
USA:
One Omega Drive, P.O. Box 4047
Stamford CT 06907-0047
ISO 9001 Certified
TEL: (203) 359-1660
FAX: (203) 359-7700
e-mail: info@omega.com
Canada:
976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928
FAX: (514) 856-6886
e-mail: info@omega.ca
For immediate technical or application assistance:
USA and Canada:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
®
Customer Service: 1-800-622-2378 / 1-800-622-BEST
®
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
®
®
Mexico and
TEL: (001)800-TC-OMEGA
FAX: (001) 203-359-7807
Latin American:
En Espa ñ ol: (001) 203-359-7803
e-mail: espanol@omega.com
Servicing Europe:
Czech Republic:
Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899
FAX: +420 59 6311114
e-mail: info@omegashop.cz
Germany/Austria:
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0
FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
e-mail: info@omega.de
United Kingdom:
One Omega Drive
River Bend Technology Centre
ISO 9002 Certified
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
e-mail: sales@omega.co.uk

Advertisement

loading

Summary of Contents for Omega iDR

  • Page 1 Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, Step 22. Store the Temperature Unit refer to the operator’s manual if needed. if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply Servicing North America: Press...
  • Page 2 Manual as well as free Software are available at explained by using the optional Remote Programmer ambient temperature (assume 75°F). www.omega.com/specs/iseries or on the CD-ROM Display (iDRP), you may also configure your device enclosed with your shipment. through the Networking or Communication option Step 2.