Setting MCU address
Set the rotary switch of the indoor unit ADDRESS on the MCU PCB same as the ADDRESS of connected indoor unit.
When installing more than 2 MCU, set each rotary switch for MCU ADDRESS properly.
MCU PCB
Indoor Unit ADDRESS
Indoor Unit
Connecting indoor with Y-Connector to MCU
In case of connecting one indoor unit to the MCU by using Y-branch joint, you must set both switches that correspond to the
MCU port with the same indoor unit address.
You must also set the DIP switch of the MCU in a same way.
Y-connector installation
Outdoor Unit PCB
Setting the number
of Indoor Unit
MCU
ADDRESS
MCU DIP S/W
MCU PCB
Indoor unit address #1
Address #2
Address #1
Setting the
number of MCU
MCU PCB
Indoor Unit ADDRESS
Indoor Unit
Indoor unit address #2
MCU
ADDRESS
MCU DIP S/W
MCU DIP S/W
17