Function blocks
Transducer Block (TB)
The Transducer Block "Analog Input (AI)" takes the original measured value (Secondary Value 2),
carries out the min./max. adjustment (Secondary Value 1), carries out a linearization (Primary Value)
and makes the values on its output available for further function blocks.
min/max
Linearization
adjustment
%
Lin%
m(d)
Sensor_Value
TB
Secondary
Secondary
Primary
Value 2
Value 1
Value
Fig. 39: Schematic presentation Transducer Block (TB)
Function block Analog Input (AI)
The function block "Analog Input (AI)" takes the original measured value selected by a Channel
Number and makes it available to additional function blocks on its output.
Fig. 40: Schematic presentation function block Analog Input (AI)
Function block Discret Input (DI)
The function block "Discret Input (DI)" takes the original measured value selected by a Channel
Number and makes it available to additional function blocks on its output.
Fig. 41: Schematic presentation function block Discret Input (DI)
Function block PID Control
The function block "PID Control " is a key component for various tasks in the process automation
70
SITRANS LG270 - Operating Instructions
PBD-51041071