Siemens SITRANS LG270 Operating Instructions Manual page 63

Guided wave radarfoundation fieldbus coax probe, minus 196...plus 280 degrees c; minus 196 ... plus 450 degrees c
Table of Contents

Advertisement

Gas phase
Temperature
Air
20 °C/68 °F
200 °C/392 °F 0.13 %
400 °C/752 °F 0.08 %
Hydrogen
20 °C/68 °F
200 °C/392 °F 0.05 %
400 °C/752 °F 0.03 %
Steam (satu-
100 °C/212 °F -
rated steam)
180 °C/356 °F 2.1 %
264 °C/507 °F 1.44 %
366 °C/691 °F 1.01 %
Characteristics and performance data
Measuring cycle time
Step response time
4)
Max. filling/emptying speed
Ambient conditions
Ambient, storage and transport tempera-
ture
Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value
always applies.
The measurement error through the process conditions in the specified pressure and temperature
range is < 1 %.
Process pressure
Vessel pressure relating to the flange
nominal pressure stage
Process temperature
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
4)
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
PBD-51041071
10 bar
50 bar
(145 psig)
(725 psig)
0.22 %
1.2 %
0.74 %
0.52 %
0.10 %
0.61 %
0.37 %
0.25 %
-
-
9.2 %
5.7 %
< 500 ms
≤ 3 s
1 m/min
Products with high dielectric constant (>10) up to 5 m/
min.
-40 ... +80 °C (-40 ... +176 °F)
-1 ... +400 bar/-100 ... +40000 kPa
(-14.5 ... +5800 psig), depending on the process fitting
see supplementary instructions manual "Flanges ac-
cording to DIN-EN-ASME-JIS"
-196 ... +280 °C (-321 ... +536 °F)
SITRANS LG270 - Operating Instructions
Pressure
100 bar
200 bar
(1450 psig)
(2900 psig)
2.4 %
4.9 %
1.5 %
3 %
1.1 %
2.1 %
1.2 %
2.5 %
0.76 %
1.6 %
0.53 %
1.1 %
-
-
-
-
-
-
13.2 %
76 %
400 bar
(5800 psig)
9.5 %
6 %
4.2 %
4.9 %
3.1 %
2.2 %
-
-
-
-
63