Indicator Description; Power Supply Specification; Environmental Specifications For Product - Haiwell H04DT User Manual

Programmable logic controller
Table of Contents

Advertisement

www.haiwell.com
2.

Indicator description

2.1 Indicator description of H04DT, H32DT
PWR:Power indicator, green. Normally on-power normal; off - power abnormal.
1
LINK: Multi-status indicator .three colors(Red. Yellow. Green) ,as follow:
2
Reference processing mode
Normal
Firmware upgrade failed, reupgrade
the module firmware
2.2 Indicator description of H04TC, H04RC, H08TC, H08RC
PWR:Power indicator, green. Normally on-power normal; off - power abnormal.
1
LINK: Multi-status indicator .three colors(Red. Yellow. Green) ,as follow:
2
Reference processing mode
Normal
Parallel power supply not enough,
must connect to external power
supply
Firmware upgrade failed, reupgrade
the module firmware
Hardware failure and maintenance
RJ45 Ethernet indicator: there are two Ethernet LEDs, green and yellow, as shown on the right picture:
3
Color
Green light is always on
Green light goes out
Yellow light blinks
Yellow light goes out
3.

Power supply specification

Item
Power supply voltage
Power supply frequency
Instantaneous surge
Power loss time
Fuse
24V Output voltage (for input and expansion)
Isolation Type
Power Protection
4.

Environmental specifications for product

Item
Temperature/humidity
Vibration resistance
Impact resistance
Interference immunity
Over voltage resistance
Insulation impedance
Operating environment
Module bus state
MPU didn't identify the module and no
communication
MPU has identified the module but no
communication
Serial(H32DT) or parallel port in communication
Without serial or parallel port in communication
With serial or parallel port in communication
Module bus state
No communication of module
MPU has identified the module but no
communication
Serial or parallel port in communication
Without serial or parallel port in communication
With serial or parallel port in communication
Without serial or parallel port in communication
With serial or parallel port in communication
Without serial or parallel port in communication
With serial or parallel port in communication
Physical connection of TCP module and external device is normal;
TCP module fails to connect with external device or the module itself is abnormal
TCP module is connected to an external device normally, and blinking frequency indicates
the data transmission speed. When speed is fast, human eye is not easy to distinguish it,
at this time, yellow light is long brignt.
No data transmission communication of TCP module and external device
DC input power polarity reverse, over voltage protection
Operating temperature:0~+55℃ Storage temperature:-25~+70℃ Humidity: 5~95%RH, No condensation
10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis
15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis
DC EFT:±2500V
Surge:±1000V
500VAC/1min between DC terminal and PE terminal
Between AC terminal and PE terminal @500VDC,>=5MΩ ,all input/output points to PE terminal @500VDC
Avoid dust, moisture, corrosion, electric shock and external shocks
Haiwell PLC - Temperature & Humidity Module User Manual
Status description
DC Power Supply
24VDC
-15%~+20%
——
MAX 20A 1.5ms @24VDC
10ms or less
0.3A,250V
None
No Electrical isolation
Environment Specification
4 / 23
LINK indicator state
No light
Constant light in green
Green jitter: indicator on 30ms and off 30ms
Red flicker: indicator on 0.5s and off 0.5s
Red is darkened and jitter alternately: indicator off
0.5s and jitter 0.5s
LINK indicator state
No light
Constant light in green
Green jitter: indicator on 30ms and off 30ms
Yellow flicker: indicator on 0.5s and off 0.5s
Yellow is darkened and jitter alternately: indicator off
0.5s and jitter 0.5s
Red flicker: indicator on 0.5s and off 0.5s
Red is darkened and jitter alternately: indicator off
0.5s and jitter 0.5s
Constant light in red
Red jitter quickly: indicator on 30ms and off 30ms
AC Power Supply
100~240VAC
50~60Hz
20A 1.5ms MAX @220VAC
20ms or less @220VAC
2A, 250V
24V, -15%~+15%, 200mA (Max)
Transformer isolation or optoelectronic
isolation,1500VAC/1 minute
DC 24V output over current protection