5.

Main parameters for modules

5.1 Main parameters for digital temperature and humidity modules

Item
Input interface
Input Quantity
Communication interface
Communication speed
Communication protocol
Power supply mode
Measured distance
Measured range
Isolation mode

5.2 Main parameters for thermal resistance and thermocouple modules

Item
Input range
Resolution
Input impedance
Maximum input range
Input indication
Response time
Digital input range
Precision
Power supply
Isolation mode
Power consumption
6.

Wiring diagram

6.1 Digital temperature and humidity module: Single / multiple DS18B20, RW1820, DS1990 sensor input wiring diagram

SHT1X, SHT7X input wiring diagram
Note:
VDD (Vdd +) and (Vdd-) are the sensor power terminals that can be wired nearby;
1
Pin connection definition of DS18B20, RW1820, DS1990, SHT1X, SHT7X sensors can be seen in respective technical
2
information;
Cables between sensor DS18B20, RW1820, DS1990 and module are recommended to use shielded 4-core twisted pair;
3
one set of cable can be connected to ground (Vdd-) and signal lines (DT), the other set of cable can be connected to power
supply and ground (Vdd-), the shield is single-point grounded at the source.
H04DT
DS18B20, RW1820, DS1990, SHT1x,
SHT7x sensor
4 Channels 4 points
None
None
None
PLC host internal power supply
≤200m(Wire resistance 50Ω)
DS18B20:-55~+125℃
SHT11:-40~+123.8℃
0~100%RH
No isolation between channels,analog & digital optical isolation
RTD input
Pt100, Pt1000, Cu50, Cu100
0.1℃
6MΩ
±13V
LED light ON means normal ,OFF means external disconnection
560ms/4 Channel, 880ms/8 Channel
16 bits, code range:0~32000
0.1% F.S
MPU use internal power supply, expansion modules use external power supply 24VDC ±10% 5VA
Optoelectronic isolation, no isolation between channels, analog & digital optical isolation
24VDC ±20%,50mA(maximum)
Haiwell PLC - Temperature & Humidity Module User Manual
DS18B20, RW1820, DS1990 sensor
2 channels, each channel 16 points
2400~115200 Baud rate
PLC host internal power supply or independent external supply of 24VDC
≤200m(Wire resistance50Ω)
DS18B20:-55~+125℃
Thermocouple input
S, K, E, J, B, N, R, Wre3/25, Wre5/26, [0,20]mV, [0,50]mV, [0,100]mV
5 / 23
H32DT
RS485
Standard Modbus
0.1℃
6MΩ
±30mA