10.2 - Electrical data, units with options 5 and 6

The electrical data of 30XW units with options 5 and 6 are
the same as for 30XW heat units with option 150. Please
refer to chapter 9.2.
10.3 - Dimensions, clearances, units with option 5
and 6
The dimensions and clearances are the same as for 30XW
units. Please refer to chapter 3.

10.4 - Operating range, units with options 5 and 6

Evaporator
Entering water temperature at start-up
Leaving temperature during operation*
Option 5 with ethylene glycol
EG 5
Option 5 with propylene glycol
PG 5
Option 6 with ethylene glycol
EG 6
Option 6 with propylene glycol
PG 6
Entering/leaving temperature difference at full load 2.8 K
Condenser
Entering water temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load 2.8 K
*
The operating range with evaporator leaving temperatures above 3°C is
permitted, but the performances are not optimised.
** For lower condenser temperatures a water flow control valve must be installed
at the condenser (two-way or three-way). Please refer to option 152 to ensure
the correct condensing temperature.
*** Please refer to chapter 10.5 for the minimum recommended evaporator glycol
flow rate.
**** Depends on the conditions at the evaporator and the load conditions.
Note: Ambient temperatures: During storage and transport of the 30XW units
(including by container) the minimum and maximum permissible temperatures are
-20°C and 72°C (and 65°C for option 200).

10.5 - Minimum recommended evaporator flow rate with options 5 and 6

Reference number
Minimum evaporator flow rate*
Minimum evaporator flow rate**
*
Recommended values with ethylene glycol at the evaporator. Minimum concentration of 25% with option 5 and of 35% with option 6.
** Recommended values with propylene glycol at the evaporator. Minimum concentration of 24% with option 5 and of 30% with option 6.
Note: The minimum flow rates are for information only. For more precise details refer to the unit selection program.

10.6 - Nominal evaporator pressure drop with options 5 and 6

Reference number
Nominal evaporator flow rate*
Nominal evaporator pressure drop*
Nominal evaporator flow rate**
Nominal evaporator pressure drop**
Option 5
*
Values based on 25% ethylene glycol, evaporator entering/leaving water temperatures of -2°C/-6°C and condenser entering/leaving water temperatures of 30°C/35°C.
** Values based on 24% propylene glycol, evaporator entering/leaving water temperatures of +1°C/-3°C and condenser entering/leaving water temperatures of 30°C/35°C.
Option 6
*
Values based on 35% ethylene glycol, evaporator entering/leaving water temperatures of -8°C/-12°C and condenser entering/leaving water temperatures of 30°C/35°C.
** Values based on 30% propylene glycol, evaporator entering/leaving water temperatures of -4°C/-8°C and condenser entering/leaving water temperatures of 30°C/35°C.
Minimum
Maximum
-
35°C
-6°C
15°C
-3°C
15°C
-12°C
15°C
-8°C
15°C
11.1 K***
13°C**
-
19°C/23°C**
55°C/63°C****
11.1 K
Option 5 (medium temperature)
P0512
P0562
l/s
17
19
l/s
17
19
Option 5 (medium temperature)
P0512
P0562
l/s
19
21
kPa 40
50
l/s
19
21
kPa 43
54
70
65
60
55
50
45
40
35
EG 6
30
PG 6
EG 5
25
20
15
-15
-10
Evaporator leaving glycol temperature, °C
Operating range permitted, but performances are not optimised
Full load with option 5/6 and ethylene or propylene glycol
Part load limit approx. 80%
Part load limit approx. 50%
Part load limit approx. 30%
Option 6 (low temperature)
P1012
-1154
P0512
36
40
14
36
41
14
Option 6 (low temperature)
P1012
-1154
P0512
40
45
14
61
75
48
40
46
15
65
81
51
PG 5
-5
0
5
10
P0562
P1012
14
27
16
31
P0562
P1012
16
29
65
77
16
30
65
81
15
20
-1154
29
32
-1154
34
107
35
115
27