Greengate ONW-P-1001-MV-W Installation Instructions

Neoswitch passive infrared (pir) single relay occupancy sensing wall switch

Advertisement

Quick Links

P/N 9850-000344-01

General Information

• Read all instructions on both sides of this
• Install in accordance with ALL local codes
sheet first
• For indoor use only
Specifications
Technology: Passive Infrared (PIR)
Coverage: Major motion – 1000 sq. ft.
Electrical Ratings
120 VAC:
Light Level Sensing: 0 to 200 foot-candles
• Incandescent/Tungsten – Max. load: 6.7 amps,
Operating Environment:
800W, 50/60 Hz
• Temperature: 32° F – 104° F (0° C – 40° C)
• Fluorescent/Ballast – Max. load: 10 amps, 1200W,
• Relative Humidity: 20% to 90% Non-condensing
Housing: Durable, injection molded housing.
50/60 Hz
Motor Load: ¼ HP @ 125 VAC
Polycarbonate resin complies with UL94VO.
277 VAC:
Size:
• Fluorescent/Ballast – Max. load: 9.8 amps,
• Mounting Plate/Strap Dimensions:
2700W, 50/60 Hz
4.195" H x 1.732" W (106.553 mm x 44 mm)
Ballast Compatibility: Compatible with magnetic and
• Product Housing Dimensions: 2.618" H x 1.752"
electronic ballasts
W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)
No Minimum Load Requirement
LED Indicators: Red LED indicates PIR detection; Green
Time Delays: Self-Adjusting, 15 seconds/test (10 min
LED acts as EcoMeter or night light locator.
Auto), Selectable 5, 15, 30 minutes

Description

The ONW-P-1001-MV Occupancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing lighting control
and conventional Wall Switch all-in-one, used for energy savings and convenience.

PIR Technology

The sensor's segmented lens divides the field of view into sensor zones, and detects the changes in temperature
that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.
The ONW-P-1001-MV allows the control of one load with one occupancy sensor switch.
The sensor can be configured to enhance energy savings by setting the unit for manual ON operation.
In Automatic ON Mode, the lights turn ON automatically when a person enters the room. In Manual ON Mode, the
lights are turned ON by pressing the universally recognized light icon Pushbutton. In either mode, the lights stay ON
as long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF automatically after
a preset Time Delay interval.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and
Time Delay in Real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential
energy savings that are available in the particular application.
The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding
individuals to take control of their lighting to maximize energy savings.
The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.
Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy. The
sensor will switch the lights ON when it detects a person entering the area. If the sensor does not continue to detect
motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute Time Delay.
NeoSwitch Passive Infrared (PIR)
Single Relay Occupancy Sensing Wall Switch
(Ground Required)

EcoMeter Operation

Load 1
EcoMeter LED
OFF
ON
ON
OFF
Minor motion – 300 sq. ft.

Coverage

The ONW-P-1001-MV is designed for offices up to 300 square feet.
,
8

Location

When installing the ONW-P-1001-MV in a new junction box, choose the switch location carefully to provide
optimum coverage of the occupied area. When replacing an existing Wall Switch, bear in mind that there must be a
clear Line-of-sight between the sensor and the area to be covered. Avoid pointing the ONW-P-1001-MV directly into the
hallway where it may detect passers-by.
Action
EcoMeter
A person enters the space and
OFF
the load is activated
The area is vacated and the
Increased awareness of energy savings;
100%
lights turn OFF automatically
Acts as a night light locator
Increased awareness of energy savings and
A person turns the lights OFF
reminds individuals to take control of their
100%
manually upon exiting an area
lighting for additional savings; Acts as a night
light locator
The daylight feature prevents
Increased awareness of energy savings and
the lights from automatically
100%
lets individual know that the daylighting
turning ON when a person
feature is working
enters an area
,
36
,
20
Minor Motion, IR
Major Motion, IR
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.

Installation Instructions

Installation

Benefit
The ONW-P-1001-MV can be installed in any standard single gang
box. It may be installed in the same manner as an ordinary Wall Switch.
• Wire the ONW-P-1001-MV as described in the wiring section.
• Mount the ONW-P-1001-MV in the junction box.

Wiring

CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked "SWD." All installations should be
in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install Wall Switch plate.
Wiring Diagram 1: 120/277 VAC single level single circuit wiring diagram
120/277 VAC
BLACK
GREEN
GROUND
NEUTRAL
Model # ONW-P-1001-MV-W
Model # ONW-P-1001-MV-V
Model # ONW-P-1001-MV-LA
Model # ONW-P-1001-MV-G
Model # ONW-P-1001-MV-B
BLUE
LOAD
Eaton's Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ONW-P-1001-MV-W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Greengate ONW-P-1001-MV-W

  • Page 1: Installation Instructions

    • Temperature: 32° F – 104° F (0° C – 40° C) • Fluorescent/Ballast – Max. load: 10 amps, 1200W, • Relative Humidity: 20% to 90% Non-condensing CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF Housing: Durable, injection molded housing. 50/60 Hz at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main Motor Load: ¼ HP @ 125 VAC...
  • Page 2 Troubleshooting Wiring Diagram 2: 120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram 1. Walk around the room and monitor LEDs. 2. Stand in different parts of the room and wave your hands. LED should only turn ON for one second with each motion. Issue Possible Causes Suggestions (If LED does not turn ON, go to Installer Adjustments – Red (PIR) Sensitivity Adjustment Section) BLUE 120/277 VAC BLACK Detection LEDs Press Pushbutton. If Auto Mode 3. Stand still three to four feet away from sensor for five PIR Lens Sensor is in Manual ON mode is desired change Activation Mode to Auto.

This manual is also suitable for:

Onw-p-1001-mv-vOnw-p-1001-mv-laOnw-p-1001-mv-gOnw-p-1001-mv-b

Table of Contents