Mitsubishi Electric FX2N-32CCL Installation Manual page 2

Melsec-f/fx2n series
Hide thumbs Also See for FX2N-32CCL:

Advertisement

INSTALLATION
PRECAUTIONS
 Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
 When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
 Be sure to remove the dust proof sheet from the PLC's ventilation port when
installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
 Make sure to attach the top cover, offered as an accessory, before turning on
the power or initiating operation after installation or wiring work.
Failure to do so may cause electric shock.
 Connect extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
2.1 Connection with PLC
The FX
2N
-32CCL connects on the right side of an PLC main unit or extension
units/blocks (including special function units/blocks).
For connection to the FX
2NC
Series PLC or an extension block of the FX
Series PLC, use an FX
2NC
-CNV-IF.
For connection to the FX
3GC
/FX
3UC
Series PLC or a special function block of the
FX
3UC
Series PLC, use an FX
2NC
-CNV-IF or FX
3UC
-1PS-5V.
For details, refer to the respective PLC user's manual hardware edition or
hardware manual.
2.2 Mounting
The product is mounted by the following method.
 DIN rail mounting
 Direct mounting (mounting screw: M4 screw)
For details, refer to the respective PLC user's manual - hardware edition or
hardware manual.
3. Specification
For details on specifications, refer to the following manual.
Refer to the FX
2N
-32CCL User's Manual.
DESIGN
PRECAUTIONS
 For the status of each station when the main unit stops calculation or when a
communication error occurs in the data link, thoroughly read the description
of data link processing time in the CC-Link master module manual. Construct
an interlock circuit in the sequence program using the communication status
information (SB, SW) so that the system always works conservatively.
Erroneous outputs and malfunctions may cause accidents.
 When executing control (data changes) to an operating PLC, construct an
interlock circuit in the sequence program so that the entire system operates
conservatively.
In addition, when executing control such as program changes and operation
status changes (status control) to an operating PLC, thoroughly read the
manual and sufficiently confirm safety in advance.
Especially in control from external equipment to a PLC in a remote place,
problems in the PLC may not be able to be handled promptly due to
abnormality in data transfer.
Construct an interlock circuit in the sequence program. At the same time,
determine the actions in the system between the external equipment and the
PLC for protection against abnormalities in data transfer.
 Make sure to include the following safety circuits outside the PLC to ensure
safe system operation even during external power supply problems or PLC
failure.
Otherwise, malfunctions may cause serious accidents.
1) Above all, the following components should be included: an emergency
stop circuit, a protection circuit, an interlock circuit for opposite
movements (such as normal vs. reverse rotation), and an interlock circuit
(to prevent damage to the equipment at the upper and lower positioning
limits).
2) Note that when the PLC main unit detects an error during self diagnosis,
such as a watchdog timer error, all outputs are turned off. Also, when an
error that cannot be detected by the PLC main unit occurs in an input/
output control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such cases.
DESIGN
PRECAUTIONS
 Observe the following items. Failure to do so may cause incorrect data-
writing through noise to the PLC and result in PLC failure, machine damage
or other accident.
1) Do not bundle the control line together with or lay it close to the main
circuit or power line. As a guideline, lay the control line at least 100 mm
(3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
2) Ground the shield wire or shield of a shielded cable. Do not use common
grounding with heavy electrical systems.
 Do not apply excessive pressure to the power supply terminal block or CC-
Link connection terminal block. Excessive pressure may cause damage or
error.
DISPOSAL
PRECAUTIONS
 Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
 The PLC is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications of the PLC main unit manual by
using dedicated packaging boxes and shock-absorbing palettes.
Failure to do so may cause failures in the PLC. After transportation, verify
operation of the PLC and check for damage of the mounting part, etc.
3.1 Applicable PLC
Model name
FX
/FX
/FX
/FX
/FX
/FX
0N
1N
2N
2NC
3G
3GC
3.2 General Specification
Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the respective PLC user's manual - hardware
2NC
edition or hardware manual.
Item
Specification
Dielectric withstand
Between external terminals as a
500 V AC for one minute
voltage
whole and ground terminal
3.3 Power Supply Specification
Item
Specification
Drive
Power supply voltage
24 V DC +10% -10%
power
Current consumption
50 mA (Supplied from external terminal)
supply
Control
Power supply voltage
5 V DC
power
Current consumption
130 mA (Supplied from PLC via extension cable)
supply
3.4 Performance Specification
Item
Specification
Station type
Remote device station
CC-Link applicable version
Ver. 1.00
Station number
1 to 64 (set by rotary switch)
N u m b e r
o f
o c c u p i e d
1 to 4 (set by rotary switch)
stations
156 Kbps/625 Kbps/2.5 Mbps/5 Mbps/10 Mbps
Transmission speed
(set by rotary switch)
Maximum total cable length
1200 m maximum
(maximum transmission
(varies depending on the transmission speed.)
distance)
For details, refer to Section 3.5.
Twisted pair cable
Connection cable
F or t h e m od e l na m e an d t h e sp ec i f i ca t i on s of t h e
recommended cable, refer to the FX
By FROM and TO instructions or direct specification
Communication with PLC
of buffer memory via the buffer memory.
Number of I/O occupied
8 points
points
*1 FX
/FX
Series PLC can use direct specification of buffer memory. Refer to
3U
3UC
the FX
/FX
/FX
/FX
/FX
Series Programming Manual - Basic &
3S
3G
3GC
3U
3UC
Applied Instruction Edition for details.
3.5 Maximum transmission distance and transmission speed
Maximum transmission distance varies depending on the transmission speed.
Remote I/O
Remote I/O
station
station
Master station
Local station
Remote
Remote
device station
device station
1)
2)
1)
Maximum transmission distance
Transmission
Maximum transmission
1)
2)
speed
156 Kbps
30 cm or more
625 Kbps
30 cm or more
2.5 Mbps
2 m or more
30 cm or more
60 cm or more
5 Mbps
30 to 59 cm
Transmission
1)
speed
1 m or more
10 Mbps
2 m or more
60 to 99 cm
30 to 59 cm
1): The cable length between the master/local station and an adjacent station should
be 2 m or more without regard to setting of the transmission speed.
2): When the transmission speed is 5 Mbps or 10 Mbps, the maximum transmission
distance varies depending on the cable length between remote I/O stations and
remote device stations.
3.6 Number of occupied station and number of remote points
In the FX
-32CCL, the number of remote points vary depending on the selected
2N
number of stations (1 to 4).
/FX
/FX
3U
3UC
 32 remote input points and 32 remote output points are available in one station.
However, the upper 16 points of the final station are occupied by the
CC-Link as the system area.
 4 read points and 4 write points are available as remote registers in one station.
Number
Remote
of
Type
input
stations
RX00 to 0F
User area
(16 points)
1
RX10 to 1F
System area
(16 points)
RX00 to 2F
User area
(48 points)
2
RX30 to 3F
System area
(16 points)
RX00 to 4F
User area
(80 points)
3
RX50 to 5F
System area
(16 points)
RX00 to 6F
User area
(112 points)
4
RX70 to 7F
System area
(16 points)
Buffer memory
BFM
No.
Buffer memory dedicated to read
#0
Remote output RY00 to RY0F (set station)
#1
Remote output RY10 to RY1F (set station)
Remote output RY20 to RY2F
#2
(set station+1)
Remote output RY30 to RY3F
#3
(set station+1)
-32CCL User's Manual.
2N
Remote output RY40 to RY4F
#4
*1
(set station+2)
Remote output RY50 to RY5F
#5
(set station+2)
Remote output RY60 to RY6F
#6
(set station+3)
Remote output RY70 to RY7F
#7
(set station+3)
#8
Remote register RWw0 (set station)
#9
Remote register RWw1 (set station)
#10
Remote register RWw2 (set station)
Local station
#11
Remote register RWw3 (set station)
#12
Remote register RWw4 (set station+1)
1)
#13
Remote register RWw5 (set station+1)
#14
Remote register RWw6 (set station+1)
distance
#15
Remote register RWw7 (set station+1)
#16
Remote register RWw8 (set station+2)
1200 m
#17
Remote register RWw9 (set station+2)
600 m
#18
Remote register RWwA (set station+2)
200 m
#19
Remote register RWwB (set station+2)
150 m
#20
Remote register RWwC (set station+3)
110 m
Maximum transmission
BFM
2)
distance
No.
Buffer memory dedicated to read
100 m
#21
Remote register RWwD (set station+3)
80 m
#22
Remote register RWwE (set station+3)
50 m
#23
Remote register RWwF (set station+3)
#24
Set value of baud rate
#25
Communication status
#26
CC-Link model code
#27
Set value of its own station No.
Set value of number of occupied
#28
#29
#30
FX Series model code (K7040)
#31
Remote
Remote
Remote
register
register
output
for write
for read
RY00 to 0F
RWr0 to 3
RWw0 to 3
「电器电子产品有害物质限制使用标识要求」的表示方式
(16 points)
(4 points)
(4 points)
RY10 to 1F
-
-
(16 points)
Note: This symbol mark is for China only.
RY00 to 2F
RWr0 to 7
RWw0 to 7
(48 points)
(8 points)
(8 points)
含有有害6物质的名称, 含有量, 含有部品
 本产品中所含有的有害 6 物质的名称, 含有量, 含有部品如下表
RY30 to 3F
-
-
(16 points)
所示。
RY00 to 4F
RWr0 to B
RWw0 to B
(80 points)
(12 points)
(12 points)
RY50 to 5F
-
-
(16 points)
部件名称
RY00 to 6F
RWr0 to F
RWw0 to F
(112 points)
(16 points)
(16 points)
RY70 to 7F
-
-
(16 points)
外壳
可编程
控制器
印刷基板
Description
本表格依据SJ/T 11364的规定编制。
Buffer memory dedicated to write
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
Remote input RX00 to RX0F (set station)
规定的限量要求以下。
Remote input RX10 to RX1F (set station)
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
Remote input RX20 to RX2F
26572规定的限量要求。
(set station+1)
Remote input RX30 to RX3F
(set station+1)
Remote input RX40 to RX4F
(set station+2)
This manual confers no industrial property rights or any rights of any other kind,
Remote input RX50 to RX5F
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
(set station+2)
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Remote input RX60 to RX6F
(set station+3)
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Remote input RX70 to RX7F
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(set station+3)
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
Remote register RWr0 (set station)
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
Remote register RWr1 (set station)
accidents, and compensation for damages to products other than Mitsubishi products.
Remote register RWr2 (set station)
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
Remote register RWr3 (set station)
Remote register RWr4 (set station+1)
Remote register RWr5 (set station+1)
This product has been manufactured as a general-purpose part for general
Remote register RWr6 (set station+1)
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Remote register RWr7 (set station+1)
Before using the product for special purposes such as nuclear power, electric
Remote register RWr8 (set station+2)
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
Remote register RWr9 (set station+2)
This product has been manufactured under strict quality control. However
Remote register RWrA (set station+2)
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
Remote register RWrB (set station+2)
Remote register RWrC (set station+3)
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Description
Buffer memory dedicated to write
Remote register RWrD (set station+3)
Remote register RWrE (set station+3)
Remote register RWrF (set station+3)
Undefined (Write is disabled.)
Undefined (Write is disabled.)
Undefined (Write is disabled.)
Undefined (Write is disabled.)
Undefined (Write is disabled.)
stations
Error code
Undefined (Write is disabled.)
Undefined (Write is disabled.)
Not available
Not available
产品中有害物质的名称及含量
有害物质
多溴
六价铬
多溴联苯
二苯醚
(Pb)
(Hg)
(Cd)
(Cr(VI))
(PBB)
(PBDE)
×