Trane 4TTR4 Installer's Manual

Trane 4TTR4 Installer's Manual

Condensing units
Hide thumbs Also See for 4TTR4:

Advertisement

18=AC51D1
:!l!i i
i
Condensing Units
4TTR4
ALL phases
of this installation
must
comply
with
NATIONAL,
STATE AND LOCAL
CODES
IMPORTANT
-- This Document
is customer
property
and is to remain
with this unit.
Please
return
to service information
pack upon completion
of work.
These
instructions
do not cover
all vmniations
in systems
nor provide
for every
possible
contingency
to be met in
connection
with installation.
All phases
of this installa-
tion must
comply
with
NATIONAL,
STATE AND LOCAL
CODES.
Should further
information
be desired
or should
particular
problems
arise which are not covered sufficiently
for the purchaser's
purposes,
the matter
should be referred
to
your installing
dealer or local distributor.
A. GENERAL
This information is intended for use by individuals
posses-
sing adequate backgrounds
of electrical and mechanical
experience. Any attempt to repair a central air conditioning
product may result in personal injury and or property
damage. The manufacturer
or seller cannot be responsible
for the interpretation
of this information, nor can it assume
any liability in connection with its use.
NOTICE:
Trane has always recommended installing
Trane approved
matched indoor and outdoor systems.
The benefits of installing
approved matched systems are
maximum
efficiency,
optimum performance and best
overafl system reliability.
These units use R-410A refrigerant
which operates at 50 to
70% higher pressures than R-22. Use only R-410A approved
service equipment.
Refrigerant
cylinders
are painted a
"Rose" color to indicate the type of refrigerant
and may con-
tain a "dip" tube to allow for charging of liquid refrigerant into
the system. All R-410A systems
use a POE oil that readily
absorbs moisture from the atmosphere.
To limit this "hygro-
scopic"
action, the system should
remain sealed whenever
possible. If a system has been open to the atmosphere
for
more than 4 hours, the compressor
oil must be replaced.
Never break a vacuum with air and always change the dri-
ers when opening the system for component replacement.
For specific handling concerns
with R-410A and POE oil, ref-
erence Retrofit Bulletin TRN-APGO2-EN.
Check for transportation
damage
after unit is uncra_d.
Report promptly,
to the carrier,
any damage found to the unit.
To determine
the electrical
power requirements
of the unit,
refer to the nameplate
of the unit.
The electrical
power
available
must agree with that listed on the nameplate.
UNiT CONTAINS R-410A REFRIGERANT!
R-410A
OPERATING
PRESSURE
EXCEEDS
THE
LIMIT
OF R-22. PROPER
SERVICE
EQUIPMENT
IS
REQUIRED.
FAILURE
TO USE PROPER
SERVICE
TOOLS
MAY RESULT
IN EQUIPMENT
DAMAGE
OR
PERSONAL
INJURY.
SERVICE
USE ONLY R-410A
REFRIGERANT
AND
APPROVED
POE COMPRESSOR
OIL.
©
5 FT. ABOVE UNiT = UNRESTRICTED
B. LOCATION
AND PREPARATION
OF THE UNiT
1. When removing
unit from the pallet, notice the tabs on
the basepan.
Remove tabs by cutting
with a sharp
tool as
shown in Figure 2 (see page 2).
2. The unit should be set on a level support
pad at least as
large as the unit base pan, such as a concrete
slab. If this
is not the application
used please refer to application
bulletin
"Trane APB2001-02".

Advertisement

Table of Contents
loading

Table of Contents