INSTRUCTION MANUAL

SPECIFICATIONS

Model
Loudspeaker
Rated Power (RMS)
Power Taps 100V
Impedance
Sensitivity
Sound Pressure
Sensitivity EN54-24
Frequency Response
Cutout Size
Dimension (mm)
Weight
Finish
Colour
Mounting
Power selection
EN54 standard
Other standards

INSTALLATION GUIDE

A-225EN Version 1.1
1k6 , 3k3
98,3 dB SPL at 1 W, 1 m IEC268-5
106 dB at 6 W, 1 m IEC268-5
74,9 dB SPL at 1 W /4 m
57 ~ 24.000 Hz
Ø 181,5 x 66 (depth)
ABS, metallic grille
White RAL 9016
Transformer tabs
Loudspeaker for voice alarm systems for fire detection and fire alarm systems for buildings
Ceiling Loudspeaker, 6W, Type A
CE-Symbol according 93/68EWG
VA special. In compliance with BS-5839, part 8.
Impedance
100 V
6 W
1k6
3 W
3k3
1,5 W
6k6 k
Common Common
1/1
CEILING SPEAKER
At WARNING:
Installation by qualified personnel only.
Speakers must be wired in parallel and connected to
the correct line terminals of amplifier.
Ensure that all speakers have the same polarity with
respect to each other.
Do not select another tapings if the speaker is in use.
No naked flame sources, such as lighted candles,
should be placed on the apparatus
A-225EN
5"
6 W
6, 3 & 1,5 W
& 6k6
Ø 150 mm
0,6 kg
Springs
EN 54-24:2008
Ref. No.: DOP_A225EN
ID-Code: A225EN
1438/CPR/0458
70 V
3 W
1,5 W
0,75 W
A-225EN
.