Article number
Relay outputs
Number of relay outputs
•
Rated supply voltage of relay coil L+ (DC)
•
Current consumption of relays (coil current
•
of all relays), max.
external protection for relay outputs
•
Number of operating cycles, max.
•
Switching capacity of contacts
–
with inductive load, max.
–
with resistive load, max.
–
Thermal continuous current, max.
–
Switching current, min.
–
Rated switching voltage (DC)
–
Rated switching voltage (AC)
Cable length
shielded, max.
•
unshielded, max.
•
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Alarms
Diagnostic alarm
•
Diagnostic messages
Monitoring the supply voltage
•
Wire-break
•
Short-circuit
•
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1)
Manual, 09/2017, A5E03576775-AE
6ES7132-6HD01-0BB1
4
24 V
40 mA
Yes, with 6A
7 000 000; see additional description in the man-
ual
2 A; see additional description in the manual
5 A; see additional description in the manual
5 A; Max. 1 385 VA, 150 W
100 mA; 5 V DC
24 V DC to 120 V DC
24V AC to 230V AC
1 000 m
200 m
No
Yes
Yes
Yes
Yes
No
No
Yes; green PWR LED
Yes; Green LED
No
Yes; green/red DIAG LED
Technical specifications
6.1 Technical specifications
25