6.5.2

Operation using buttons

Introduction
This overview informs you about the most important safety notes to be observed when
operating the pressure transmitter. Furthermore, the overview guides you in adjusting the
operating functions on site.
Condition
The keyboard must have been unlocked in order to operate the device using the buttons.
Procedure
In the default setting, the device is in the measured value display.
To adjust the operating functions, proceed as follows:
1. Loosen both the screws of the keyboard cover and lift it upwards.
2. Keep pressing the [M] button until the desired mode is displayed.
3. Keep pressing the [↑] or [↓] button until the desired value is displayed.
4. Press the [M] button.
5. Close the keyboard cover using the two screws.
See also
Releasing key lock or function lock (Page 96)
6.5.3

Start of scale value/full scale value

6.5.3.1

Difference between setting and adjusting

Introduction
In "Pressure" measuring mode, you can set or adjust the start of scale value and full scale
value using the buttons. Modes 2 and 3 are used for this. Rising and falling characteristic
curves can be realized with appropriate use of the buttons. If the transmitter is not in
"Pressure" measuring mode, this mode is skipped in local operation.
SITRANS P DS III with HART
Operating Instructions, 06/2013, A5E00047092-09
Now you have saved the values and the device goes to the next mode.
Note
The setting is saved and the measured values are automatically displayed again if more
than two minutes have passed after a button was pressed for the last time.
Operation
6.5 Local operation
79