Handling; Technical Data; Test Conditions And Correction Factors - York VCH-25A Installation Manual

Large split air - air vitality series air conditioners
Hide thumbs Also See for VCH-25A:
Table of Contents

Advertisement

1
Installation manual
1.4

Technical data

The air conditioner shall be deposited in the area established by local authorities, to facilitate its selective
recovery.

1.3.4 Handling

The unit must be moved using the metal rails provided for its installation and transport.
1.4 Technical data

1.4.1 Test conditions and correction factors

Test conditions
Length of connec‐
tion
Voltage
pipes
[m]
400
7,5
Correction factors for cooling capacities
Cooling capacity correction factors for different air flows to the nominal flows in the indoor coil
% Flow
Total capacity
Sensible capacity
Comp. absorbed power
Cooling capacity correction factors according to length and height between units
Vertical distance between the indoor unit and
H
the outdoor unit
Equivalent length of pipes between the indoor
L
unit and the outdoor unit
E
(consider a single line)
A
Outdoor unit above indoor unit
B
Indoor unit above outdoor unit
1
Indoor unit
2
Outdoor unit
4
Summer
Out. temp. °C
Ind. temp. °C
DB
TH
DB
35
24
27
80
90
0,96
0,98
0,945
0,973
0,98
0,99
Winter
Out. temp. °C
TH
DB
TH
19
7
6
100
110
1
1,016
1
1,038
1
1,009
A
B
B
A
2
2
1
Ind. temp. °C
DB
TH
20
12
120
130
1,032
1,046
1,075
1,118
1,017
1,025
1