Profibus Cable; Cio-777-Pr Specifications - SymCom CIO-777-PR Programming Manual

Profibus communications module
Table of Contents

Advertisement

Profibus Cable

The Profibus Cable must be connected as follows:
Pin
1
2
3
4
5
6
7
8
9
FIGURE 3: 9-Pin Sub-D
Connector Pin Assignment
Power Requirements
Voltage
Current
Power
Weight
Enclosure
Terminal (depluggable terminal block)
Torque
Wire AWG
Safety Marks
UL
CSA
Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity, Radiated
Fast Transient Burst
Hi-Potential Test
Environmental
Temperature Range
Class of Protection
Relative Humidity
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Signal
Description
–––
–––
–––
–––
RxD/TxD-P
Receive/Transmit data; line B (red)
CNTR-P
Control of repeater direction
DGND
Data ground (reference voltage to VP)
-
VP
Power supply +5V (e.g. bus termination)
–––
–––
RxD/TxD-N
Receive/Transmit data; line A (green)
-----
------

CIO-777-PR SPECIFICATIONS

12–24VDC
150mA (max.)
3.6 Watts (max.)
3 oz.
Polycarbonate
4.5 in.-lbs. (max.)
12–20 AWG
UL508 (File #E68520)
C 22.2
IEC 1000-4-2, Level 3, 6kV contact, 8kV air
159 MHz, 10V/m
IEC 1000-4-4, Level 3, 4 kV input power
Meets UL508 (2 x rated V +1000V for 1 minute)
Ambient Operating: -20 to 70 C (-4 to 158 F)
Ambient Storage: -40° to 80°C (-40° to 176°F)
IP20, NEMA 1 (Finger Safe)
10-95%, non-condensing per IEC 68-2-3
1 2 3 4 5