ABB MicroSCADA Pro SYS 600C Product Manual page 39

Table of Contents

Advertisement

1MRS756804
MicroSCADA Pro
Product Guide
Function
Reports Workpace with
data logging
The following list shows some examples when IEDs are connected to SYS 600C with
the following Gateway or NCC connections and with Local process database:
NCC connection with one DNP serial communication including 100 IEDs resulting
in 1 200 process updates per second sent to one NCC
NCC connection with two DNP LAN communications including 67 IEDs resulting
in 1 600 process updates per second sent to two NCCs
NCC connection with one IEC 104 LAN communication including 158 IEDs resulting
in 1 900 process updates per second sent to one NCC
NCC connection with two IEC 104 LAN communications including 116 IEDs res-
ulting in 2 800 process updates per second sent to two NCCs
The following list shows some examples when IEDs are connected to SYS 600C with
Local process database and displayed with Workplaces:
60 IEDs with IEC 61850 protocol and 1 Workplace with 1 050 display objects
63 IEDs with IEC 61850 protocol and 2 Workplaces both including 450 display
objects
77 IEDs with IEC 61850 protocol and 1 Workplace including 150 display objects
Impact on process com-
munication
- 1%
SYS 600C 1.92
Comments
Per Workplace with Measurement
Reports with 15 min report
Total of 900 objects data logged by
Measurement Reports
39

Hide quick links:

Advertisement

Table of Contents
loading