Emi/Ems And Environmental Standard Compliance - ABB MicroSCADA Pro SYS 600C Product Manual

Table of Contents

Advertisement

SYS 600C 1.92
6.2.
34
MicroSCADA Pro
Product Guide

EMI/EMS and environmental standard compliance

The following tables list the EMI/EMS and environmental standard compliance.
Table 6.2-1 IEC 61850-3 standard compliance
Type test
IEC 61000-4-2-2001
IEC 61000-4-3-2006
IEC 61000-4-4-2004
IEC 61000-4-5-2005
IEC 61000-4-6-2006
IEC 61000-4-8-2001
IEC 61000-4-10-1993
IEC 61000-4-12-1995
IEC 61000-4-16-2002
IEC 61000-4-29-2000
CISPR22-2008
FCC 15
EN55022A
IEC 60255-5
IEC 60255-27
Table 6.2-2 IEEE Std 1613-2003 standard compliance
Type test
IEEE C37.90.1
IEEE C37.90.3
IEEE C37.90.1
IEEE C37.90
IEEE C37.90
IEC 60870-2-1-1995
Description
Electrostatic Discharge
Radiated RF Succeptibility
Fast Transient (Burst Immunity)
Surge Immunity
Conducted RF Immunity
Magnetic Field Immunity
Damped Magnetic Immunity
Damped Oscillatory Burst
Conducted RF Immunity
Voltage Dips & Interrupts
Conducted and Radiated
Emissions
Conducted and Radiated
Emissions
Conducted and Radiated
Emissions
Insulation resistance measure-
ment
Protective bonding resistance
Description
EFT
ESD
Oscillatory Wave
Dielectric Strength
Impulse Voltage
DC Voltage Ranges
1MRS756804
Severity level
Level 4 -±8KV Contact/±15KV
Air
Level 3-18V/m, 6 directions
Level 4- ±4KV 5KHz
Level 4 ±4KV line-to-
earth/±2KV line-to-line
Level 3-10Vrms
Level 5- 100A/m 5min /
1000A/m 1s
Level 4- 30A/m
Level 3-2.5KV common/Differ-
ential 1.25KV for Substation
Level 3-15Hz~150KHz
30% 120ms/ 70% 10ms 100%
3ms (cycle 3)
Class A
Class A
Class A
500VDC, 1min,
999Mohm>100Mohm
25Amps, 1min,
0.021ohm<0.1ohm
Severity level
Level 4- ±4KV 5KHz All ports
Level 4 -±8KV Contact/±15KV
Air
Level 3-2.5KV common/Differ-
ential 1.25KV for Substation
2000Vrms
5000V
-20%~+15%