I. Operational Checks: Temperature Control Operation, Conventional Controls
Minimum discharge air temp setpoint (°F) __________________________________________________
Maximum discharge air temp setpoint (°F) __________________________________________________
___ Low temperature limit switch opens.
___ All circuit check lights illuminate properly.
___ The time clock controls operate properly (if applicable).
___ The cycle/cooldown stat operates properly (if applicable).
J. Operational Checks: Temperature Control Operation, Intelligent Controls
___ Check and record the following:
Room Sensor
Measured Temperature ____________
Temp on PC after calibration ____________
Outdoor Air
Measured Temperature ____________
Temp on PC after calibration ____________
Discharge Air
Measured Temperature ____________
Temp on PC after calibration ____________
Minimum discharge air temp setpoint (°F) __________________________________________________
Maximum discharge air temp setpoint (°F) _________________________________________________
Comments __________________________________________________________________________
K. Operational Checks: Damper Control (Check options which apply.)
___ Burner supply air damper operates properly.
___ Building pressure transducer output between Vout and Com at 0" w.c. is 2.50 VDC.
___ Building pressure control setpoint is at (factory-recommended) .01" w.c. positive.
___ Outside air/return air dampers respond properly to pressure controls, manual damper control and/or
summer ventilation thermostat.
___ Discharge dampers
___ Exhaust dampers
Comments ___________________________________________________________________________