Rapid 4044 Installation, Operation & Service Manual page 153

Rapid 4000 series direct-fired air handler
Table of Contents

Advertisement

SECTION 25: RAPID
®
4000-S
S
-U
P
ERIES
TART
P
ROCEDURES
G. Operational Checks- Fan Operation
__ Fan rotation is correct. (See rotation sticker in the unit.)
__ Check and record the following:
Volts (Fan Off)
Phase 1-2 ___
Phase 2-3 ___
Phase 1-3 ___
Volts (Fan On)
Phase 1-2 ___
Phase 2-3 ___
Phase 1-3 ___
Running Amps
Phase 1 ___
Phase 2 ___
Phase 3 ___
Differential pressure drop across burner. (Measured at AFS tubing test ports.) 20% OA ___
100% OA ___
H. Operational Checks- Burner Operation
Inlet Standing Gas Pressure (in. w.c.) _____________________________________________________
___ Pilot is approximately the size of a baseball.
Pilot Line Pressure (in. w.c.) _____________________________________________________________
Flame Signal Relay (VDC) ______________________________________________________________
___ Low re gas pressure produces a minimum continuous ribbon of flame.
Burner High Fire Gas Pressure (in. w.c.) ___________________________________________________
Forced High Fire Inlet Gas Pressure (in. w.c.) _______________________________________________
Forced High Fire Mod. Gas Valve Volts (VDC) _______________________________________________
High Fire Burner Flame Length (in.) _______________________________________________________
Flame Color _________________________________________________________________________
___ Low airflow switch opens on pressure drop. (Setpoint at .2" w.c.)
___ High airflow switch opens on pressure rise. (Setpoint at 1.35" w.c.)
___ High temperature limit switch opens on temperature rise.
___ Low gas pressure limit switch opens on pressure fall.
___ High gas pressure limit switch opens on pressure rise.
___ Manifold gas leak test.
___ Burner responds properly to room temperature setpoint changes.