M-system Current Loop Supply M3LDY Installation Manual page 3

B&b electronics current loop supply installation manual
Hide thumbs Also See for Current Loop Supply M3LDY:
Table of Contents

Advertisement

EXTERNAL & INTERNAL VIEWS
FRONT VIEW
10 11 12
7
8
9
1
2
3
4
5
6
CONFIGURATION MODE & DIP SW SETTINGS
When you program the transmitter module, two configura-
tion modes are available: Field Configuration using DIP SW
/ control buttons, and PC Software. (The Option B type is for
the field configuration only.)
The internal DIP switches are used to configure input and
output type. Once the module is configured, precise ranges
are set up with the front control buttons using a simulator
connected to the input terminals and a multimeter connected
to the output terminals as a reference.
The calibrated input and output ranges are stored in the
internal memory. The module reads the DIP-switch-cali-
brated configuration only once after the power supply is
turned on. Set the switches with the power supply removed.
Selectable I/O type and ranges are listed in Table 5 and 6.
DIP SW CONFIGURATION MODE
Turn the SW2-8 OFF to enable the DIP SW (Field Configura-
tion) mode as shown in Table 1.
See Table 2 to configure the input and Table 3 for the output.
PC CONFIGURATION MODE
Turn the SW2-8 ON to enable the PC Configuration mode as
shown in Table 1. All programmable features can be set up
on a PC regardless of other DIP SW setting except that the
output type must be selected with the DIP SW1-1 through
SW1-4 (See Table 4).
For detailed information on the PC configuration, refer to the
M3CON instruction manual.
INPUT TYPE & RANGE
INPUT TYPE
DC Current
OUTPUT TYPE & RANGE
OUTPUT TYPE
DC Current
DC Voltage, Narrow Spans
DC Voltage, Wide Spans
LED1 (LD1)
LED2 (LD2)
LED3 (LD3)
MODE Button
UP Button
DOWN Button
Configurator Jack
MINIMUM SPAN
1mA
250mV
1V
SIDE VIEW
Configuration DIP SW
4 3 2 1
OFF
ON
8 7 6 5 4 3 2 1
OFF
ON
OFF
ON
CONFIGURATION MODE (SW2)
MODE
DIP SW
PC
INPUT TYPE (SW2 & 3)
INPUT TYPE
DC current
(isolator use)
2-wire loop
(DC supply use)
OUTPUT TYPE (SW2 & 1)
OUTPUT
0 – 20mA
-2.5 – +2.5V
-10 – +10V
OUTPUT TYPE / PC CONFIG (SW1)
OUTPUT
0 – 20mA
-2.5 – +2.5V
-10 – +10V
MINIMUM SPAN
2mA
MAXIMUM RANGE
0 to 20mA
-2.5 to +2.5V
-10 to +10V
SW1
SW2
SW3
SW2-8
Configuration mode can be
OFF
confirmed with the front LED.
ON
SW2-7
ON
OFF
SW2-4 SW2-3 SW1-4 SW1-3 SW1-2 SW1-1
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
SW1-4
SW1-3
SW1-2
OFF
ON
ON
OFF
ON
OFF
MAXIMUM RANGE
0 to 20mA
CONFORMANCE RANGE
0 to 24mA
-3 to +3V
-11.5 to +11.5V
P. 3 / 6
M3LDY
Table 1
Table 2
SW3
OFF
ON
Table 3
OFF
OFF
OFF
ON
ON
OFF
Table 4
SW1-1
OFF
OFF
OFF
ON
ON
OFF
Table 5
Table 6
EM-2664 Rev.2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Current Loop Supply M3LDY and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents